Great Lakes Air Products EDR-C2 series Manuale di istruzioni - Pagina 3
Sfoglia online o scarica il pdf Manuale di istruzioni per Deumidificatore Great Lakes Air Products EDR-C2 series. Great Lakes Air Products EDR-C2 series 8. Compressed air dryer. refrigeration type high inlet temperature
PROPER USE OF DRYER
This dryer has been designed, manufactured and tested to separate humidity normally contained in
compressed air only. Any other unauthorized use will be considered improper. The manufacturer will void
the warranty and not be held responsible for any problem arising from improper use. The correct use
requires adherence to installation conditions specified in this manual.
This dryer is supplied tested and fully assembled. The only operation left to the user is the connection to
the plant in compliance with the instructions given in the following chapters.
RECEIVING EQUIPMENT
Immediately upon receipt of equipment, remove all crating and packaging around equipment. Examine
machinery for any damages either external or internal that may have occurred in transit.
If there is any physical damage or a refrigerant leak, (suction/analyzer gauge reads zero) please note
all damages on bill of lading during delivery. If damage is detected after the equipment delivery; contact
the local terminal to report all damages and file a claim immediately with the transportation company. The
carrier is legally responsible for any damages, since the unit is shipped F.O.B.
INSTALLATION LOCATION PIPING & CONNECTION
Particular care is required in selecting the installation site, as an unsuitable location could
jeopardize the proper operation of the dryer. This unit is not suitable to be used in an
explosive atmosphere, or where the risk of fire could be present.
The unit should be installed in an area that is clean and dry, allowing sufficient space on all sides for
routine maintenance and service. It should be located on a level floor or shelf free from vibrations and
sufficient to support the total weight of the machinery. Although the dryer package is a freestanding unit,
it may be secured by bolting the base to the floor but is not required. This standard dryer is designed
for indoor installation. Contact distributor if installing unit outdoors.
Installations at altitudes above 4000 feet (1219 meters) will experience a loss of capacity and may require
field adjustments of pressure settings. The unit has been factory adjusted to operate up to 4000 feet
(1219 meters), and if installation is above this altitude, contact your local distributor for correct refrigerant
settings.
Allow (2') two feet, minimum clearance around the dryer for maintenance access and adequate free
circulation of cooling air to the dryer. The ambient temperature around the dryer must not exceed 110°F
(37.7°C) or be less than 50°F (10°C).
Ambient temperatures below 40°F (10°C) require optional equipment specified below. Sufficient
ventilation must be provided to maintain acceptable ambient for efficient operation. Consider heat
rejection when locating dryer.
ELECTRICAL CONNECTION
The Nameplate/Data plate located on each unit identifies the power supply requirements and
maximum fuse specification. Units supplied with cord and plug requires the installation of a
receptacle rated for 15 amps. Units supplied with electrical junctions, require a suitable fused
disconnect in compliance with the National and Local Electrical Code requirements.
The wiring of all functional electrical components has been completed and tested at the factory in
accordance with the electrical wiring schematic provided with this manual.
Page 3