ADELSYSTEM CBI6012A Manuale di istruzioni - Pagina 2

Sfoglia online o scarica il pdf Manuale di istruzioni per UPS ADELSYSTEM CBI6012A. ADELSYSTEM CBI6012A 5. Dc ups

Battery Config - Life test – Fast Charge – UPS Disabling-
19
Time Buffering
20
Aux4: Ethernet
21
Network Communication LED
22
ADELBus (CAN)
23
Rectifier Alarm
PE for Aux4 "Shield"
24
Connection terminal and wiring
The following cable cross-sections may be used:
Solid
Stranded
(mm2)
(mm2)
In:
0.2–2.5
0.2–2.5
Out:
0.2–2.5
0.2–2.5
Signal:
Screw type terminals, 2.5 mm2. Wiring shall be marked to indicate the
proper connection for the power supply. Use copper cables only; for
power connections use wires suitable for at least 75°C
Input and Output Battery connection
Input AC Port L – N:
No.10: Single phase Switching Power Supplies L, N, PE
Battery Connection and Load Connection
Battery Connection Port:
No.1:
-Connect the battery between: terminal 3 (–) and 4 (+)
-One battery (12 Vdc) for CBI12xx;
-Two battery (12 Vdc) connected in Series for CBI24xx;
Output Load:
No.2: Connect this output to the load, terminal 1 (–) and 2 (+).
Drive and Monitoring
Fault - Status conditions
STATUS: Mains or Backup: Input Mains On/Off.
No.5 Output Open Collector Contact: 1
No.6: LED
Fault Battery or Fault System
No.4 Output Open Collector Contact: 2
No.7: LED
No.8: Led DIAGNOSIS: Diagnosis of the system through
"blinking code" light signal
Fault Internal Rectifier
No.23 Output Open Collector Contact: 3
Driver Contact open drain:
Mains/Back-Up
Port N°5
Closed
ON
Mains Input Vac
OFF
Open
YES
Open
Battery SOC
less than 30%
NO
Open
YES
Battery or
system Fault?
NO
Stripping Length
Torque
AWG
(Nm)
24 – 14
0.5–0.6
7 mm
24–14
0.5–0.6
7 mm
AMP Modu II
Open drain referred to the Load
negative terminal; requires an external
DC power source (max 48Vdc) – drain
current: 20 mA Nom ; 40 mA Max for 3
sec
Battery or System fault
Led N°6
Port N°4
Led N°7
■ - led off
■ - led off
Closed
■ - led On
■ - led off
Closed
■ - led On
■ - led On
Open
■ - led On
■ - led off
Closed
■ - led off
■ - led On
Open
■ - led off
■ - led off
Closed
Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy
Tel. +39 0522 345518 – Fax +39 0522 345551 –
Charging Mode Status
Status
Float
Absorption
Charging Type
Bulk
Recovery
Faulty Battery / Faulty System
Reverse polarity or high battery Voltage
(over 32.5Vdc for CBI 24xxA)
Battery not connected
Battery element in Short Circuit
Overload or short circuit on the load
Bad battery; Internal impedance Bad or Bad battery wire connection
Life test not possible
Rectifier Alarm
Boost condition; battery discharge after 4 min. of overload.
Low battery (under 18.5Vdc for CBI 6024A) Only if started from
battery, no mains input
Mains detector failure
Device over-temperature Alarm
Calibration error
Start from Battery No Input Mains Vac
No. 9: Push-button, max 3 sec., in the front panel to switch ON
the system without the "Mains input Vac" but only the battery
connected. Same function for additional external Button by
connection of pin N°12 (SB). The other side of the external
button must be connected to Negative Load.
Load ON/Off
It is possible to Drive the output Load On/Off by Ethernet connection. This
function allows to switch On/Off the load output for many application as,
Reset PLC, staircase light timer control, emergency light controls, etc...
Charging Current limiter:
In order to protect the battery from excessive
charging currents, the device allows to limit the
maximum charge current by Push Button. Press
button (9) for 2 sec., after that in 20 step it is
possible to select the limit current. Press for
more than 2 sec. to store the selection in
permanent memory.
CBI6024A: from 0 – 3A ; 20 step; 1 step 150mA
CBI6012A: from 0 – 5A ; 20 step; 1 step 250mA
It is possible set the limiting current also by the internal Web Server,
please refer to the Ethernet section.

Battery Care

The Battery Care philosophy is based on algorithms that implement rapid
and automatic charging, battery charge optimization during time, flat
batteries recovery and real time diagnostic during installation and
operation. Elements in short circuit, accidental reverse polarity
connection, disconnection of the battery, can easily be detected and
removed by help of Blink Code of Diagnosis Led, during the installation
and after sale. Each device is suited for all battery types, it is possible to
set predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd,
Li-Ion. They guarantee battery reliability over time by continuously testing
the internal impedance status, avoiding any possible risk of damage and
granting a permanent, reliable and safe connection of the battery to the
power supply. The system includes a battery stimulation circuit and
sophisticated algorithms to recognize sulphated batteries or batteries
with a short-circuited element. Battery Test: Automatic. battery
connection check: every 60 seconds. Battery efficiency test: every 220
minutes in float charge. Battery Faults can be monitored by relay and led
blinking.
Battery Charge in Temperature compensated
environment
No. 11 Auxiliary Output "AUX 1"
It is possible to connect the Temperature sensor probe and apply it on
the battery.The function of the probe is for temperature battery
compensation. With this it is possible to meet the requirements of the
EN54- fire certification.
www.adelsystem.com
Instruction Manual CBI60_4
Diagnosis (No.8)
Battery fault (No.7)
1 Blink/2 sec
OFF
1 Blink/sec
OFF
2 Blink/sec
OFF
5 Blink/sec
OFF
1 Blink/pause
2 Blink/pause
3 Blink/pause
4 Blink/pause
5 Blink/pause
6 Blink/pause
7 Blink/pause
8 Blink/pause
10 Blink/pause
12 Blink/pause
14 Blink/pause
16 Blink/pause
Page 2