ADEMCO 1025 Manuale di istruzioni per l'installazione - Pagina 5
Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione per Sistema di sicurezza ADEMCO 1025. ADEMCO 1025 6.
Other available accessories include:
No. 245 Remote Station Adapter and Supervised Fire Circuit:
Permits the addition of up to 4 remote keyswitch sta-
tions on a 2 wire circuit, momentary panic switches (e.g.: No. 219) and a supervised fire circuit to the control.
Current
Draw: 7 ma plus 9.5 ma per remote station plus Current for smoke or combustion detector power and No. 633
to
_<, ..,
Supervisory Module.
No. 262 Fire Module:
Permits the addition of an unsupervised fire circuit to the control.
Current Draw: 0 ma plus cur-
rent for smoke or combustion detector power.
No. 263 Supervised Fire Module:
Permits the addition of a supervised fire circuit to the control with optional No. 706
Mini-Howler annunciation of fire trouble.
Current Draw: 5 ma plus current for smoke or combustion detector
power and No. 633 Supervisory Module.
No. 688 Opening/Closing Switching Module:
Interfaces between the control and a digital communicator to signal
the communicator to send opening and closing messages as the control is disarmed and armed.
Current Draw: 2 ma
with high impedance constant load.
No. 1034 Zone Expansion Center:
Permits additional protection zones to be added to the control by expanding a sin-
gle protection zone to 4 zones (including a "day" zone option on 2 of the zones).
Current Draw: 20 ma.
No. 1035 Day Zone Adapter:
Permits the addition of a "day" or "24 hour" zone to the control with day sounder annun-
ciation of disturbances.
Current Draw: 6 ma.
Complete information accompanies the above accessories.
-
SPECIFICATIONS
Physical: .
Width:
6" (20.3 cm)
Height: 15" (38.1 cm)
Depth:
3" ( 7.6cm)
c
Electrical:
Voltage: 12V. AC (from No. 1320 Plug-in Transformer)
Current (per loop): 4 ma
Maximum Resistance (per loop): 300 ohms
6V. DC Bell Circuit Output: 2 A maximum (incl. accessories)
(3 A Fuse, No. 90-l 2)
6V. DC Accessories Circuit Output: 220 ma max. continuous
;-
2 A max. on alarm (incl. bell circuit)
,!
(3 A Fuse, No. 90-l 2)
Output Relay Contacts: SPST, Rating: 2 A at 26V. DC, 11OV. AC
r
Standby: 6V Sealed Lead Acid Rechargeable Battery, 2.5 A.H. (Ademw
No. 496) Up to 60 hrs. standby, dependent upon continuous
load supplied to accessories.
I--
~~~-~~~
- .-- -~~ ~
MAXIMUM STANDBY TIMES WfTH VARIOUS
1
AUXILIARY CIRCUIT CONTINUOUS LOADS'
ma:
0
50
100
150
200
220
Hrs:
60
26
14
9.5
7
6
*Loads in addition to control panel and loop currents.
I
CAUTION
Digital Communicators
(or Dialers) shall not be set or programmed to place a call to a police station
number which has not been specifically assigned by that police station for such service.
I
510
50.1