DAYLIFF DG 950P Manuale d'installazione e d'uso - Pagina 7
Sfoglia online o scarica il pdf Manuale d'installazione e d'uso per Inverter DAYLIFF DG 950P. DAYLIFF DG 950P 12.
Anche per DAYLIFF DG 950P: Manuale d'installazione e d'uso (12 pagine)
4. ELECTRICAL CONECTIONS
If the generator is to be connected for standby power use
ensure a qualied electrician is employed. The generator must
be isolated from the utility power when connected or serious
WARNING
damage will result to the generator and house power circuits.
Ensure total load does not exceed the generator rating. Maximum power output must
Ÿ
only be used briefly or generator damage will occur.
Ensure total load does not exceed the generator rating. Maximum power output must
Ÿ
only be used briefly or generator damage will occur.
DC output to be used for charging automotive and solar 12V batteries only. Ensure
Ÿ
correct polarity when connecting cables, i.e +ve to +ve and -ve to -ve generator to
battery terminals.
Ensure the generator is properly earthed. Consult a qualified electrician if in doubt.
Ÿ
5. GENERATOR OPERATION
Always start generator before applying load by switching the
circuit breaker and stop the generator after disconnecting
load. Starting and stopping under load will damage the
WARNING
generator and powered accessories.
CHECK ENGINE OIL. Operating without oil will cause severe engine damage and
Ÿ
invalidate the warranty.
To start ensure ignition 'ON', fuel valve 'ON' and choke 'ON'. Then either pull starter
Ÿ
cord (manual start) or turn key (electric start). For electric start do not turn the engine
on for more than 5 seconds. If ti fails to start release the switch and wait 15 seconds
before re-trying. Switch off choke when engine has started.
Check output voltage is 240V on the voltmeter. If not adjust engine speed. If the speed
Ÿ
setting is correct and the voltage is low then the generator is overloaded and load must
be reduced.
If more than an appliance is connected apply load progressively with greatest load
Ÿ
first.
Close fuel valve whenever generator is not operating.
Ÿ
DG950 generators use two-stroke engines and oil must be pre-mixed with petrol at
Ÿ
the ratio of 50:1. Use fuel tank cap as an oil measure adding one inverted capfull for
each litre of fuel. Engine damage will occur without pre-mixed oil.
6. ROUTINE MAINTENANCE
For Diesel engines see separate engine manual. The below instructions apply to petrol
versions only.
ENGINE OIL
Check engine oil daily. If low refill with SAE30.
Ÿ
4