You can monitor the status of the HOA
switches through SuperVision by assigning
each switch a digital input in the FB using
channel numbers 81 through 96. Channel 81
corresponds to HOA switch number one;
channel 82 corresponds to HOA switch two,
and so on. Switches 10 through 15 use
channel numbers 8A through 8F, and switch
16 uses channel number 80.
An off status on these channels means the
HOA switch is in Auto mode. An on status
means the HOA switch is in Manual mode.
Channel Numbers
The following tables show the valid channel
numbers for each point on the MX16160.
Enter the channel number, offset, and gain for
each point in Eikon before the Function Block
is made, or on the FB's Parameter page in
SuperVision. If an offset and gain are not
provided here, use SuperVision's Point
Configuration or Point Help feature to
determine the offset and gain.
Table 3. Digital Output Channel Numbers
Channel
Point
Signal Type
Number
Digital
11
DO 1
HOA Status†
81
Digital
12
DO 2
HOA Status†
82
Digital
13
DO 3
HOA Status†
83
Digital
14
DO 4
HOA Status†
84
Digital
15
DO 5
HOA Status†
85
Digital
16
DO 6
HOA Status†
86
Digital
17
DO 7
HOA Status†
87
Digital
18
DO 8
HOA Status†
88
Digital
19
DO 9
HOA Status†
89
Digital
1A
DO 10
HOA Status†
8A
Digital
1B
DO 11
HOA Status†
8B
Revised 9/13/00 • MX16160
Table 3. Digital Output Channel Numbers
Channel
Point
Signal Type
Number
Digital
1C
DO 12
HOA Status†
8C
Digital
1D
DO 13
HOA Status†
8D
Digital
1E
DO 14
HOA Status†
8E
Digital
1F
DO 15
HOA Status†
8F
Digital
10
DO 16
HOA Status†
80
† Use digital input microblocks to
monitor the status of HOA Switches.
Table 4. Input Channel Numbers
Channel
Point
Signal Type
Number
Thermistor
31
UI 1
mA or Volts
31
Digital
21
Thermistor
32
UI 2
mA or Volts
32
Digital
22
Thermistor
33
UI 3
mA or Volts
33
Digital
23
Thermistor
34
UI 4
mA or Volts
34
Digital
24
Thermistor
35
UI 5
mA or Volts
35
Digital
25
Thermistor
36
UI 6
mA or Volts
36
Digital
26
Thermistor
37
UI 7
mA or Volts
37
Digital
27
6
© 2000 Automated Logic Corporation
†Range
Offset
Gain
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V