Celec 98MDC Manuale - Pagina 5
Sfoglia online o scarica il pdf Manuale per Controllore Celec 98MDC. Celec 98MDC 9. Mdi-controller
MDI-CONTROLLER
98MDC
11.
- To set Alarm1 percentage
Again press
Example:-
12.
- To set Alarm2 percentage
Again press
12.
- To set Trip percentage
Again press
Example:-
13.
- To Test outputs
Again press
14.
- To set Integration
Again press
15.
- To Manipulating Error
Again press
key, Display shows
,
If user set target demand at 160 kW and AL1 is at 110
Then over load limit will be 160x110/100 = 176 kW
As the running load exceeds 176 Alarm1 will be ON.
Use
and
keys to set Alarm1 value.
key, Display shows
, it is the percentage value of running demand period at which Alarm2 will
be on full normal period.
Example:-
If user set target demand at 160 kW and AL2 is at 95
There limit for Alarm2 will be 160x95/100 = 152 kW
As Rising Demand (RD) reaching 152 Alarm2 will be ON.
Use
and
keys to set Alarm2 value.
key, Display shows
be on full normal period.
If user set target demand at 160 kW and Trip is at 100
There limit for Alarm2 will be 160x100/100 = 160 kW
As Rising Demand (RD) reaching 160 Trip will be working 5 seconds.
Use
and
keys to set Trip value.
key, Display shows
Use
key, Display show
Again press
key, Display show
Again press
key, Display show
key, Display shows
,
Use
and
keys to set integration time 15 and 30 minutes.
Suit the Integration time equal to energy meter Integration time usual it is 30 minutes
key, Display shows
,
hence RD running demand will match automatically.
Use
and
keys to increase and decrease value.
= 100 - actual controller calibration
= 110 - 10% addition to the actual controller calibration
= 90
- 10% below actual controller calibration
Note:-
Measurement should be stimulation from controller and energy meter for matching.
Alarm1 energizes when kW More than Set MD.
, it is the percentage value of running demand period at which Trip will
and AL1 LED glows, and Alarm1 on in 10 seconds.
and AL2 LED glows, Alarm2 on in 10 seconds.
and Trip LED glows, Trip on in 5 seconds.
it should be equal to energy meter.
This feature is for matching controller kW with energy meter kW and
User Manual
.
.
.