DynaGen GSC400 Series Manuale dell'utilità di calibrazione - Pagina 9

Sfoglia online o scarica il pdf Manuale dell'utilità di calibrazione per Controllore DynaGen GSC400 Series. DynaGen GSC400 Series 18. For generator
Anche per DynaGen GSC400 Series: Manuale del programmatore (4 pagine)

DynaGen GSC400 Series Manuale dell'utilità di calibrazione
9 of 18

3.2 Manual Calibration

AC Voltage Calibration
If the voltage only varies a little from the system voltage a simple offset
adjustment is sufficient. When the voltage offset calibration constant is
decremented by 1 the actual voltage reading is decremented by 0.1VAC. The
calibration constants range from -126 to 126.
If adjusting the voltage offset is not enough the voltage slope calibration
constants can also be adjusted. Increasing the value of the slope constants
decreases the value of the voltage reading.
AC Current Calibration
It is recommended to use the wizard to calibrate the current. See below.