8– OPTIONS

2G: 2 synchronous gas contacts

The DGPT2
is equipped with two Reed contacts, whose triggering thresholds are
®
identical.
The Reed contacts' characteristics are identical to the Reed contact equipping the
Standard DGPT2
.
®
Conforming to IEC EN 50216:3 Standard, the Reed contacts change position when
the gas inside the transparent body reaches a volume between 100 and 200 cm

2GD: 2 gas contacts with an offset

The DGPT2
is equipped with two Reed contacts, whose triggering thresholds are
®
offset by 40 cm
approximately.
3
Conforming to IEC EN 50216:3 Standard, the Reed contacts change position when
the gas inside the transparent body reaches a volume between 100 and 200 cm

2P: 2 synchronous pressure contacts

The DGPT2
is equipped with a pressure switch
®
with 2 microcontacts, whose triggering thresholds
are identical.
The triggering threshold is defined by the
customer.
2PD: 2 pressure contacts with an offset
The DGPT2
is equipped with a pressure switch
®
with 2 microcontacts, whose triggering thresholds
are offset.
Defined at the time of the order, this offset (10 to
100 mbar) cannot be modified by the customer
afterwards.
The value indicated on the pressure switch's setting
system is the lowest triggering threshold (P1).
CE: industrial connector
The DGPT2
is equipped with a Harting connector
®
on the cover enabling the user to connect or
disconnect the wiring system while the metal
housing remains closed.
TECH. INSTRUCTIONS
DGPT2
®
A U T O M A T I O N 2 0 0 0
Page
13
N° T/NOT-0021
Date: 28/09/16
.
3
.
3
Rev.
7