HID Aero X1100 Manuale di installazione

Sfoglia online o scarica il pdf Manuale di installazione per Controllore HID Aero X1100. HID Aero X1100 8. Intelligent controller

HID Aero X1100 Manuale di installazione
I NSTA LLAT ION G UI DE
HID Aero™ X1100
Intelligent Controller
Up to 4 Readers, 7 Inputs, 4 Outputs
Supplied parts
ƒ HID Aero X1100 Intelligent Controller (1)
ƒ Installation guide (1)
ƒ Mounting screws (4) 0.138" × 1" (3.5 mm × 25 mm)
ƒ Casing screws (4) 0.118" × 0.75" (3 mm × 20 mm)
Recommended parts
(not supplied)
ƒ Certified DC power supply
ƒ Drill with various bits for mounting hardware
ƒ For DIN rail mounting: Brackets (2) - Phoenix Contact,
USA 10 Series Rail Adapter, part number 1201578.
Screws (4) - Self tapping, countersunk,
3.0 mm × 10 mm (or 3.0 mm × 8 mm)
X1100 Overview
The X1100 performs intelligent access control operations, input monitoring and output control for up to:
64 readers, 64 doors, 615 inputs, 388 outputs.
DIP SWITCH
See step 6.
READERS 1-2
See step 4.
"
4.53
(115 mm)
INPUTS 1-4
See step 7.
RELAYS 1-4
See step 5.
© 2019 - 2020 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID Brick logo, the Chain Design, HID Aero, and HID Signo are trademarks or registered
trademarks of HID Global, ASSA ABLOY AB, or its affiliate(s) in the US and other countries and may not be used without permission. All other trademarks, service marks, and
product or service names are trademarks or registered trademarks of their respective owners.
hi d gl ob a l.com
CABLE REQUIREMENTS (NOT SUPPLIED)
Host–Ethernet
Readers–OSDP
Readers–
Wiegand / C&D
IO Modules*
Alarm Inputs
Power and Relays
*VertX wire specifications are compatible with X1100. Utilize existing
VertX V100, V200 and V300 RS-485 wiring when attaching to X1100.
POWER, TAMPER, AC FAIL, BATT FAIL
See step 8.
"
5.51
(140 mm)
An ASSA ABLOY Group brand
PLT-04233, Rev. A.3
CAT-5, 328 ft (100 m)
4 conductor twisted pair over-all shield,
Belden 3107A or equivalent. 2000 ft
(610 m) maximum. Utilize one pair for
data and one pair for power
4-conductor, 18 AWG, shielded, 500 ft
(150 m) maximum
One twisted pair, shielded. 120Ω
impedance, 24 AWG, 4,000 ft
(1,219 m) maximum
One twisted pair, 30Ω maximum,
typically 22 AWG, 1000 ft (304.8 m)
2-conductor shielded
18 to 16 AWG, 500 ft (150 m)
Status LEDs
See page 6
READERS 1-2
See step 4.
INPUTS 1-4
See step 7.
RELAYS 1-4
See step 5.
IO MODULE PORTS
See step 3.