AutomationDirect Productivity2000 P2-16DAL-1 Manuale di avvio rapido - Pagina 2

Sfoglia online o scarica il pdf Manuale di avvio rapido per Sistemi I/O AutomationDirect Productivity2000 P2-16DAL-1. AutomationDirect Productivity2000 P2-16DAL-1 8. Analog output

General Specifications

Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
10000mW (Loop Power Included)
Enclosure Type
Open Equipment
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System ONLY. See "Wiring Options"
Field Wiring
on page 5. Must use copper conductors 75°C or
equivalent.
See the "EU Directive" topic in the Productivity Suite
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type
24-Pin Molex Style 43025-2400
Weight
90g (3.2 oz)
UL 61010-1 and UL 61010-2-201 File E139594, Canada
and USA
Agency Approvals
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-
201 Safety)*
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com

Output Specifications

Output Channels
Module Signal Output Range
Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Output Type (sourcing)
Output Value in Fault Mode
Load Impedance
Maximum Inductive Load
Allowed Load Type
Maximum Inaccuracy
Maximum Full Scale Calibration Error (Including
Offset)
Maximum Offset Calibration Error
Accuracy vs. Temperature
Max Crosstalk at DC, 50/60Hz
Linearity Error (End to End)
Output Stability and Repeatability
Output Ripple
Output Settling Time
All Channel Update Rate
Maximum Continuous Overload
Field to Logic Side Isolation
Type of Output Protection
Output Signal at Power Up and Power Down
External DC Power Required
Tech Support 770-844-4200
16
4–20 mA sourcing
12-bit
4-20 mA = 3.9 μA / count
1 LSB = 1 count
0 to 4095 counts
Current: 20mA max
Less than 4mA
0–570 Ω (19.2 VDC), 0–690 Ω (21.6 VDC),
0–810 Ω (24VDC), 0–930 Ω (26.4 VDC),
0–1100 Ω (30VDC)
Minimum Load: 0Ω @ 0–45°C
125Ω @ 45–60°C ambient temperature
1mH
Grounded
1% of range (Including Temperature Drift)
±0.2% of range minimum
±0.2% of range maximum
±75 PPM / °C maximum full-scale calibration change
(±0.005% of range / °C)
-72dB, 1 LSB
±4 LSB max., (±0.1% of full scale)
Monotonic with no missing codes
±2 count after 10 min. warm up (typical)
±0.1% of full scale
0.3ms max., 5µs min. (full scale range)
1ms
Outputs open circuit protected
1800VAC applied for 1 second (100% tested)
Electronically current limited to 20mA or less
4mA
24VDC @ 410mA (includes loop power)