HIDRIA 0314-4-0089 Manuale di istruzioni per l'uso - Pagina 4

Sfoglia online o scarica il pdf Manuale di istruzioni per l'uso per Ventilatore HIDRIA 0314-4-0089. HIDRIA 0314-4-0089 9. Fan with electronically commutated external-rotor motor

03

OPERATING CONDITIONS

The fans are rated for S1 (IEC 60034-1) continuous operation.
Extreme ON-OFF switching operating must be avoided, because it has negative influence on life expectancy and power consumption.
Cycling operating mode should only with cycling ON/OFF via control signal (0/10V analog input or PWM input).
Do not cycling the power supply for cycling operating mode – use control signal! High 'In-rush current' can occur during cycling power supply!
Permissible ambient temperature is stated to the specified operating points - see appended 'Performance curves' for actual fan. If actual load deviates
from specified operating point, motor temperature-rise should be checked.
Figures on the motor name-plate refer to nominal values according to EN 60335 if not otherwise specified (EN 60335, 'free air', 'max.load', 'max.eff.',
cust. unit / cust. spec., UL, IEC 60034-1).
Continuous sound pressure level may exceed 70dBA (depends of fan model).
If an already installed fan is switched OFF for a long period in a humid atmosphere, it should be switched ON for minimum of two hours every month to
remove any moisture that may have condensed inside the motor.
Protection (motor & electronics): IP54 according to EN60529.
Power consumption in stand-by mode: les than 5W.
DIMENSIONS
Nominal diameter: 560 mm - see Appendix - technical drawing: VENTILATOR / R14R-56APS-ET60B-03B18
Weight: 13,4 kg
NOMINAL DATA - defined according to ' MAX.LOAD '
Phase: 3~
Nominal Voltage: 400 V
Operating Voltage range: 380-460 V
Frequency: 50-60 Hz
Input power: 600 W
Nominal current: 1,1 A
Rotational speed: 1150 RPM
Operating ambient temperature range: -25°C .. +60°C
Altitude: 2000 m
Insulation class: 130
Protection provided by PE: Class I
Overvoltage category (OVC): II
Operating humidity ambient: up to 95% (non condensing).
Max. pressure: 130 Pa
ErP DATA
Overall Efficiency, Effes: 50,2 %
Installation category: A
Efficiency category: static
Efficiency grade, N: 57,8
Variable speed drive: INTEGRATED
Power Input , Pelec: 630,1 W
Airflow volume , qV: 6608 m³/h
Pressure Increase, ps: 160 Pa
Rotational Speed, n: 1157 RPM
Specific ratio: 1,002
Airflow volume max., qV: 10141 m³/h
Pressure Increase max., ps: 359 Pa
© Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
USER'S GUIDE R14 AXIAL FAN , Code: 0000, Iss: 9.07.2019
An example of a label and explanation of the content:
1
2
3
8
7
1. Fan type and code
2. Trade mark and manufacturer address
3. Nominal values (Voltage, frequency, Electric Power, Current...)
4. Certification marks
5. Date of production (week of the year/year)
6. QR code which includes code number, production date, serial number and
link to website.
7. Data acc. to EU regulation 327/2011 (ErP)
8. NOTE INDICATE TO WHICH STANDARD/RULES CORESPOND DATA ON THE
NAMEPLATE:
- EN 60335-1 : Name-plate data are made according to standard EN 60335-
1, Household and similar electrical appliances – Safety – Part 1 :
10.1 If an appliance is marked with rated power input, the power input at
normal operating temperature shall not deviate from the rated power
input by more than: + 20% if Pn<300W or +15% (or 60W whichever is the
greater) if Pn>300W.
10.2 If an appliance is marked with rated current, the current at normal
operating temperature shall not deviate from the rated current by more
than: +20% if In<1.5A or +15% (or 0,30A whichever is the greater) if
In>1.5A.
- FREE AIR : Data on the nameplate established at a point 0Pa static
pressure.
- MAX LOAD : Data on the nameplate established at a point of maximal
static pressure regarding max. ambient
- MAX. EFF. : Data on the nameplate established at a point of maximal
static efficiency.
- CUST. UNIT / CUST. SPEC. : Data on the nameplate specified according to
customer specifications or at working point in customer's unit .
- UL - Data on the nameplate defined according to specifications in UL
standards.
- IEC 60034-1 - Data on the nameplate established at a point of nominal
load according to standard for Rotational electrical machines.
4
5
6
temperature
.
4 / 9