Tighten the flare nut with a wrench.
Torque wrench
Indoor unit tubing
Capacity
(Btu/h)
GAS
1/2"[5.5kg . m]
18K, 24K, 26K
5/8"[6.6kg . m]
When extending the drain hose at the indoor unit,
install the drain pipe.
Drain pipe
Vinyl tape(narrow)
Adhesive
Wrap the insulation material around the
F
connecting portion.
Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
Plastic bands Insulation material
Spanner (fixed)
Flare nut
Connection pipe
Pipe Size[Torque]
LIQUID
1/4"[1.8kg . m]
3/8"[4.2kg . m]
Indoor unit drain hose
Wrap the area which accommodates the rear
piping housing section with vinyl tape.
Connection
pipe
Vinyl tape
(wide)
Connecting cable
Vinyl tape(narrow)
Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range
within which they fit into the rear piping housing
section.
Wrap with vinyl tape
Pipe
Drain hose
For right rear piping
Route the indoor tubing and the drain hose to
A
the required piping hole position.
Insert the piping, drain hose and the connecting
B
cable into the piping hole.
8
Indoor
unit pipe
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Connecting cable
Drain pipe