Autonics TC4S Manuale - Pagina 9

Sfoglia online o scarica il pdf Manuale per Regolatore di temperatura Autonics TC4S. Autonics TC4S 14. Touch switch type temperature controller
Anche per Autonics TC4S: Manuale (14 pagine), Manuale (2 pagine), Manuale di istruzioni (2 pagine), Manuale di avvio rapido (9 pagine), Manuale di avvio rapido (10 pagine)

Autonics TC4S Manuale
TC Series

Functions

Alarm [ AL-1 / AL-2 ]

Alarm operation

Mode
Name
-
AM)_
Deviation
high-limit
AM!
alarm
Deviation
low-limit
AM@
alarm
Deviation
high/low-limit
AM#
alarm
Deviation
high/low-limit
AM$
reserve alarm
Absolute
value high
AM%
limit alarm
Absolute
value low
AM^
limit alarm

Sensor break Alarm -

SBa
Loop break Alarm
LBa
※ H: Alarm output hysteresis [ AHYS ]

Alarm option

Mode
Name
Standard alarm
AM .A
Alarm latch
AM .B
Standby sequence1
AM .C
Alarm latch and
AM .D
standby sequence1
Standby sequence2
AM .E
Alarm latch and
AM .F
standby sequence2
※ Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set
temperature, alarm temperature[ AL1 , AL2 ] or alarm operation[ AL-1 , AL-2 ], switching STOP mode to RUN mode.
Sensor break alarm
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature
controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between
standard alarm [ SBaA ], or alarm latch [ SBaB ].
H-62
AM!A
Alarm
operation
Alarm operation
-
OFF
H
ON
SV
PV
100℃
110℃
High deviation: Set as 10℃
ON
H
OFF
PV
SV
90℃
100℃
Lower deviation: Set as 10℃ Lower deviation: Set as -10℃
ON
H
OFF
PV
SV
90℃
100℃
Lower deviation: Set as 10℃, High deviation: Set as 20℃
OFF
H
ON
PV
SV
90℃
100℃
Lower deviation: Set as 10℃, High deviation: Set as 20℃
OFF
H
ON
PV
SV
90℃
100℃
Absolute-value Alarm:
Set as 90℃
ON
H
OFF
PV
SV
90℃
100℃
Absolute-value Alarm:
Set as 90℃
-
Description
If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON status.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the
second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied
and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition,
alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON.
After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence1. It operates not only by power ON/OFF,
but also alarm setting value, or alarm option changing. When re-applied standby sequence and if it is
alarm condition, alarm output does not turn ON.
After clearing alarm condition, alarm latch operates.
There are two alarms which operate individually. You can set
combined alarm operation and alarm option. Use digital input
Alarm
key(set as AlRE ) or turn OFF power and re-start this unit to
option
release alarm operation.
Description
No alarm output
OFF
H
ON
If deviation between PV and SV as high-limit is
higher than set value of deviation temperature,
PV
SV
90℃
100℃
the alarm output will be ON.
High deviation: Set as -10℃
ON
H
OFF
If deviation between PV and SV as low-limit is
higher than set value of deviation temperature,
SV
PV
100℃
110℃
the alarm output will be ON.
H
ON
If deviation between PV and SV as high/low-limit
is higher than set value of deviation temperature,
PV
120℃
the alarm output will be ON.
H
OFF
If deviation between PV and SV as high/low-limit
is higher than set value of deviation temperature,
PV
the alarm output will be OFF.
120℃
OFF
H
ON
If PV is higher than the absolute value,
SV
PV
the output will be ON.
100℃
110℃
Absolute-value Alarm:
Set as 110℃
ON
H
OFF
If PV is lower than the absolute value,
SV
PV
the output will be ON.
100℃
110℃
Absolute-value Alarm:
Set as 110℃
It will be ON when it detects sensor disconnection.
It will be ON when it detects loop break.