Autonics TC4W Manuale - Pagina 11

Sfoglia online o scarica il pdf Manuale per Regolatore di temperatura Autonics TC4W. Autonics TC4W 14. Touch switch type temperature controller
Anche per Autonics TC4W: Manuale (14 pagine), Manuale (2 pagine), Manuale di istruzioni (2 pagine), Manuale di avvio rapido (9 pagine), Manuale di avvio rapido (10 pagine)

Autonics TC4W Manuale
TC Series
Loop break alarm (LBA)
It checks control loop and outputs alarm by temperature change of the subject. For heating control (cooling control), when
control output MV is 100% (0% for cooling control) and PV is not increased over than LBA detection band [ LBaB ] during
LBA monitoring time [ LBaT ], or when control output MV is 0% (100% for cooling control) and PV is not decreased below
than LBA detection band [ LBaB ] during LBA monitoring time [ LBaT ], alarm output turns ON.
Temperature
monitoring time
SV
Control
LBA detection
output
MV
100%
0%
Loop break
alarm (LBA)
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB ] during LBA monitoring
Start control to ①
time [ LBaT ]
①to②
The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB ] during LBA monitoring
②to③
time [ LBaT ], loop break alarm (LBA) turns ON after LBA monitoring time.
③to④
Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.
④to⑥
The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 100% and PV is not increased over than LBA detection band [ LBaB ] during LBA monitoring
⑥to⑦
time [ LBaT ], loop break alarm (LBA) turns ON after LBA monitoring time.
When control output MV is 100% and PV is increased over than LBA detection band [ LBaB ] during LBA monitoring
⑦to⑧
time [ LBaT ] loop break alarm (LBA) turns OFF after LBA monitoring time.
⑧to⑨
The status of changing control output MV (LBA monitoring time is reset.)
※ When executing auto-tuning, LBA detection band [ LBaB ] and LBA monitoring time are automatically set based on auto
tuning value. When AL1, AL2 alarm operation [ AL-1 , AL-2 ] is set as loop break alarm (LBA) [ LBa ], LBA detection
band [ LBaB ] and LBA monitoring time [ LBaT ] parameter is displayed.
SSR drive output function (SSRP function) [SSrM]
● S SRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing standard SSR drive
output.
● Realizing high accuracy and cost effective temperature control as linear output(cycle control and phase control).
● Select one of standard ON/OFF control [STND], cycle control [CYCL] , phase control [PHAS] at [SSrM] parameter of
Parameter group 2. For cycle control, connect zero cross turn-on SSR or random turn-on SSR. For phase control,
connect random turn-on SSR.
Power
100-240VAC
50/60Hz
※ When selecting cycle or phase control mode, the power supply for load and temperature controller must be the same.
※ In case of selecting cycle [ CYCL ] or phase [ PHAS ] control mode for PID control, control cycle [ T ] is not allowed to set.
※ For AC/DC power model (TC4 - 2R), this parameter [ SSrM ] is not displayed and it is available only standard control
by relay or SSR.
H-64
LBA
LBA
monitoring time
PV
LBA detection
band
band
LBA
invalid
Temperature controller
(TC4 Series)
SSR drive output
(12VDC)
LBA
LBA
monitoring time
monitoring time
LBA detection
band
LBA
invalid
③ ④
SSR Module
INPUT
LBA
monitoring time
LBA detection
band
LBA
invalid
Time
Load
LOAD