Autonics KN-1000B Series Manuale del prodotto - Pagina 6
Sfoglia online o scarica il pdf Manuale del prodotto per Strumenti di misura Autonics KN-1000B Series. Autonics KN-1000B Series 6. Bar graphic temperature indicators
Function: High / Low-limit scale value
This function is to display setting of particular high / low-limit value in order to
display high / low-limit value of measured input.
If measured inputs are a and b and particular values are A and B, it will display a = A,
b = B as below graphs.
Display
Display
value
value
B
A
a
b
Input
value
Display
Display
value
value
B
a
b
a
Input
value
A
Function: Alarm
Set both alarm operation and alarm option by combining.
88* 8
Each alarm operates individually in two alarm output models.
Alarm
Alarm
When the current temperature is out of alarm range, alarm clears
operation
option
automatically.
■ Operation
Name
Alarm operation
-
-
OFF
H
ON
Deviation
SV
PV
high limit
100℃
110℃
High deviation: Set as 10℃ High deviation: Set as -10℃
ON
H
OFF
Deviation
PV
SV
low limit
90℃
100℃
Low deviation: Set as 10℃
Sensor break -
■ Option
Name
Description
Standard
If it is an alarm condition, alarm output is ON. If it is a clear alarm
alarm
condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON
Alarm latch
status.
First alarm condition is ignored and from second alarm
Standby
condition, standard alarm operates. When power is supplied
sequence
and it is an alarm condition, this first alarm condition is ignored
and from the second alarm condition, standard alarm operates.
Alarm
If it is an alarm condition, it operates both alarm latch and
latch and
standby sequence. When power is supplied and it is an alarm
standby
condition, this first alarm condition is ignored and from the
sequence
second 1alarm condition, alarm latch operates.
Segment Table
The segments displayed on the product indicate the following meanings. It may differ
depending on the product.
7 Segment
11 Segment
0
I
0
0
I
0
I
1
J
1
1
J
1
J
2
K
2
2
K
2
K
3
L
3
3
L
3
L
4
M
4
4
M
4
M
5
N
5
5
N
5
N
6
O
6
6
O
6
O
7
P
7
7
P
7
P
8
Q
8
8
Q
8
Q
9
R
9
9
R
9
R
A
S
A
A
S
A
S
B
T
B
B
T
B
T
C
U
C
C
U
C
U
D
V
D
D
V
D
V
E
W
E
E
W
E
W
F
X
F
F
X
F
X
G
Y
G
G
Y
G
Y
H
Z
H
H
Z
H
Z
Display
value
B
B
A
a
b
A
a
b
Input
value
B
b
Input
A
value
• H: Alarm output hysteresis
Description
No alarm output
If deviation between PV and
OFF
H
ON
SV as high-limit is higher
than set value of deviation
PV
SV
90℃
100℃
temperature, the alarm
output will be ON.
If deviation between PV
ON
H
OFF
and SV as low limit is higher
than set value of deviation
SV
PV
100℃
110℃
temperature, the alarm
Low deviation: Set as -10℃
output will be ON.
It will be ON when it detects
sensor disconnection.
12 Segment
16 Segment
I
0
I
0
0
I
0
I
J
1
J
1
1
J
1
J
K
2
K
2
2
K
2
K
L
3
L
3
3
L
3
L
M
4
M
4
4
M
4
M
N
5
N
5
5
N
5
N
O
6
O
6
6
O
6
O
P
7
P
7
7
P
7
P
Q
8
Q
8
8
Q
8
Q
R
9
R
9
9
R
9
R
S
A
S
A
A
S
A
S
T
B
T
B
B
T
B
T
U
C
U
C
C
U
C
U
V
D
V
D
D
V
D
V
W
E
W
E
E
W
E
W
X
F
X
F
F
X
F
X
Y
G
Y
G
G
Y
G
Y
Z
H
Z
H
H
Z
H
Z
Input
value
Condition
of re-apply
-
-
Power ON
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com | +82-51-519-3232 | [email protected]
-