Specifications

PSAN-
PSAN-
Model
□V01C□□-□
□01C□□-□
Pneumatic type model: Gauge pressure
Pressure Type
Fluid type model: Gauge pressure
Pressure
Negative
Static
Min display unit
0.1 kPa
0.1 kPa
Rated pressure
0.0 to -101.3
0.0 to 100.0
range
kPa
kPa
Display & setting
5.0 to -101.3
-5.0 to 110.0
pressure range
kPa
kPa
Display type
7 Segment LED, 4 ½ digit
Display accuracy
-10 to 0 ℃: ≤ ±1% F.S., 0 to 50 ℃: ≤ ±0.5% F.S.
Rated pressure
Rated
Max. pressure
×2
pressure ×2
01) Only for static pressure, rated pressure range 100.0 kPa model
02) The unit is sealed structure. It is based on atmospheric pressure 101.3 kPa.
Applicable
Pneumatic type
medium
(air, non-corrosive gas)
Connection type
Connector type
Cable
Ø 4 mm, 5-core, 2 m
Wire spec.
AWG24 (0.08 mm, 40-core), insulator diameter: Ø 1 mm
Front case: PC
Back case: (back port) PC /
Material
(bottom port) PBT+GF15%
Pressure port: Brass-nickel plated
Protection
Connector type: IP40 (IEC standard)
structure
Certification
ᜢ ᜹ ᜫ
Unit weight
Back port: ≈ 80 g (≈ 165 g)
(packaged)
Bottom port: ≈ 85 g (≈ 170 g)
12 - 24 VDCᜡ (ripple P-P: ≤ 10%)
Power supply
Allowable voltage
90 to 110% of rated voltage
range
Current consumption
≤ 50 mA
01)
Control output
NPN open collector output / PNP open collector output model
Load voltage
≤ 30 VDCᜡ
Load current
≤ 100 mA
Residual voltage
NPN: ≤ 1 VDCᜡ, PNP: ≤ 2 VDCᜡ
Hysteresis
According to output operation mode
Repeat error
±0.2% F.S. ±min display interval
Response time
2.5, 5, 100, 500, 1000 ms
Protection circuit
Output short over-current protection circuit
Insulation resistance
≥ 50 MΩ (500 VDCᜡ megger)
Dielectric strength
Between the charging part and the case: 1,000 VACᜠ 50 / 60 Hz for 1 min
1.5 mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction
Vibration
for 2 hours
Ambient temperature
-10 to 50 ℃, Storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
30 to 80%RH, Storage: 30 to 80%RH (no freezing or condensation)
01) Current output: ≤ 75 mA
02) Refer to 'Output operation mode'. ±1digit error may occur due to pressure unit operation.
Analog output
Voltage (1 - 5 VDCᜡ ±2% F.S)
Output impedance
1 kΩ
Linearity
≤ ±1% F.S
Zero-point
≤ 1 VDCᜡ ±2% F.S.
Span
≤ 4 VDCᜡ ±2% F.S.
Resolution
1/1000 or 1/2000 (different by pressure type and display unit)
Response time
50 ms
Minimum Display Interval
Pressure
Negative
Min display interval 0.1 kPa
Resolution
1/1000 1/2000 1/1000 1/2000 1/1000 1/2000 1/1000 1/2000
Display unit
MPa
-
-
kPa
0.1
-
kgf/cm
0.001
-
2
bar
0.001
-
psi
-
0.01
mmHg
-
0.4
inHg
-
0.02
mmH
O
0.1
-
01)
2
01) Multiply display value by 100.
PSAN-
PSAN-□1□□□-□
□C01□□□-□
or sealed gauge pressure
01)
Compound
1 kPa
0.1 kPa
-101.3 to 100.0
0 to 1,000 kPa
kPa
-101.3 to 110.0
-101.3 to 1,100 kPa
kPa
• Pneumatic type:
Rated pressure ×1.5
Rated pressure
• Fluid type: Rated
×2
pressure ×2
Fluid type (non-corrosive gas
and fluid that do not corrode
stainless steel 316L)
Cable type / connector type
Connector type: Ø 4 mm, 5-core, 2 m
Cable type: Ø 4 mm, 5-core, 3 m
Front case: PC
Back case: PA6
Pressure port: SUS304/SUS316L
Connector type: IP40 (IEC standard)
Cable type: IP65 (IEC standard)
Connector type: ≈ 88 g (≈ 173 g)
Cable type: ≈ 90 g (≈ 167 g)
02)
Current (DC 4 - 20mA ±2% F.S)
-
≤ ±1% F.S
≤ DC 4 mA ±2% F.S.
≤ DC 16 mA ±2% F.S.
70 ms
Static
Compound
0.1 kPa
1 kPa
0.1 kPa
0.001
-
0.001
-
-
0.1
-
1
-
-
0.001
-
0.01
-
-
0.001
-
0.01
-
-
-
0.01
-
0.1
-
-
-
-

Mode Setting

[M] for over 3 sec
[M]
02)
[▼]+[▲] for over 1
RUN
sec after remove the
external pressure
[▲] for over 3 sec
01) Max. / Min. pressure value is available to check by monitoring.
[Option external input model] Auto shift judgment level checking / setting is available when P-9 External input
terminal is set as SHFT. (no input displays 0)

Parameter Setting

• Some parameter are activated / deactivated depending on other parameters. Refer to
the description.
• The setting item name and setting value are cross-displayed on the display part.
• It returns to RUN mode when there is no additional key input for 60 sec in each
parameter group.
• Guaranteed write life: 100,000 times
• [M] key: Saves setting value and moves to next parameter
] key: Selects setting value
[▼], [▲
Parameter
P-1
Display unit
OUT
P-2
operation
mode
P-3
Output type
Response
P-4
time
Voltage low
P-5
limit scale
Voltage high
P-6
limit scale
Current low
P-7
limit scale
Current high
P-8
limit scale
External
P-9
input
terminal
Auto shift
P-10
output
01)
P-11 Lock
01) Condition: P-9. External input terminal SHFT setting
-
0.1
0.001
0.001
0.02
0.8
0.03
0.1
Parameter group
Preset setting
Zero-point
adjustment
Max / Min monitoring
/ Auto shift
01)
Display Default Setting range
[Negative / Compound pressure model]
kPa, KGC: kgf/cm
, bar, psi, mmHg, inHg, H2O: mmH
2
KPA
[Static pressure model]
UNIT
MPa, kPa, KGC: kgf/cm
MPA
HYS.M: Hysteresis
WIN: Window comparison output
HY-W: Hysteresis-Window comparison output
OUtM
OFF
AUTO: Auto sensitivity setting
F.OUT: Forced output control
OUT1
1O2O Normally open
1O2C Normally closed Normally open
NoNC
1O2O
1C2O Normally closed Normally open
1C2C Normally closed Normally closed
@5 2.5, 5.0, 100, 500, 1,000 ms
SPD
[Option voltage output model]
Min. rated pressure ≤ Low limit scale ≤ 90% of rated
A-1V
)0
pressure
[Option voltage output model]
Low limit scale setting value + 10% of rated pressure
A-5V
10)0
≤ High limit scale ≤ Max. rated pressure
[Option current output model]
Min. rated pressure ≤ Low limit scale ≤ 90% of rated
A-04
)0
pressure
[Option current output model]
Low limit scale setting value +10% of rated pressure ≤
A-20
10)0
High limit scale ≤ Max. rated pressure
[Option external input model]
HOLD: Hold
D-IN
HOLD
SHFT: Auto shift
[Option external input model]
OUT1, OUT2, ALL
ShOT
OUT1
LOC1: Parameter, preset, zero-point adjustment setting
lock / Monitoring value reset lock
LOC2: Parameter lock (available to check setting value)
LOCK
LOC1
OFF
[M] for over 3 sec
[M]
RUN
Displays 0.0 and
returns automatically
[M]
Reset or set: [▼]+[▲]
for over 1 sec
O
2
, bar, psi
2
OUT2
Normally open