DynaQuip JE Series Manuale di avvio rapido - Pagina 2
Sfoglia online o scarica il pdf Manuale di avvio rapido per Controllore DynaQuip JE Series. DynaQuip JE Series 2. Multi-voltage on-off smart electric actuators
Anche per DynaQuip JE Series: Manuale del prodotto (2 pagine)
Setting the control signal format
In the modulating version of the JE actuator, DIP switches are employed to set the format of the control signal input/ output as follows:
CALIBRATION PROCEDURE
1
Push dip switch '1' up, to 'ON'
2
Connect the grey power Din plug and apply external power
3
Pull dip switch '1' down . The actuator will now make a complete operation to auto-calibrate and set the zero and span.
4
Set the dip switches according to the diagrams below to configure the DPS for control signal and command on the loss of the
control signal.
5
Apply the control signal and test. On conclusion of a satisfactory test, the modulating actuator is ready for use
4-20mA
4mA - CLOSE / 20mA - OPEN
0-10V
0V - CLOSE / 10V - OPEN
1-10V
1V - CLOSE / 10V - OPEN
CLOSE ON LOSS OF
CONTROL SIGNAL
JE Multi-colour LED status light:
Actuator operational status
No power being supplied
Actuator in MANUAL mode
Torque limiter activated
Actuator with DPS (2015) positioner
In the interest of product improvement, specifications may change without notice.
DIP SWITCH SETTINGS
4mA - OPEN / 20mA - CLOSE
0V - OPEN / 10V - CLOSE
1V - OPEN / 10V - CLOSE
OPEN ON LOSS OF
CONTROL SIGNAL
LED Colour
Off
Flash
If closing when activated = flash
Opening = flash
JE Series Modulating Electric Actuators
if opening = flash
Closing = flash
Stationary =
194566 REV C