Autonics LE4SA Manuale - Pagina 14
Sfoglia online o scarica il pdf Manuale per Timer Autonics LE4SA. Autonics LE4SA 17. Din w48xh48mm digital backlight lcd timer
Anche per Autonics LE4SA: Istruzioni (18 pagine)
LE4S Series
LE4SA Output Operation Mode
Mode
Time chart
[
OND
]
OND
ON Delay
1. Timing operation starts when power is ON.
2. Time limit output will be ON when timing operation is progressed up to the setting time. Display value will be
3. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes
4. If pressing RESET key, display value and time limit output will be reset.
[
ONd2
]
ONDⅡ
ON Delay 2
(One-shot output)
1. Timing operation starts when power is ON.
2. Time limit output will be ON during Tout setting time and goes OFF when timing operation is progressed up to
3. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes
4. If pressing RESET key, display value and time limit output will be reset.
5. Tout setting range: 0.01 sec to 99.99 sec
[
FLK
]
FK
Flicker
(Toff operation
precedes)
1. Control output will be repeatedly OFF during Toff setting time and will be ON during Ton setting time when
Ton, Toff > Ta
2. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes
3. If pressing RESET key, display value and time limit output will be reset.
4. It is able to set each Toff time and Ton time separately. In [
[
FLk1
]
FKⅠ
Flicker 1
(Ton operation
precedes)
1. Control output will be repeatedly ON during Ton setting time and will be OFF during Toff setting time when
2. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes
3. If pressing RESET key, display value and time limit output will be reset.
4. It is able to set each Ton time and Toff time separately. In [
※ Initial status: UP mode-display value is "0", output is "OFF". DOWN mode-display value is "setting time", output is "OFF".
※ Instantaneous contact (OUT2) will be returned when power is off.
※ RESET key is locked for default set and release the lock to use.
N-36
T
POWER
※ RESET
Time limit contact
(⑧-⑥)
Instantaneous contact
(①-③)
Setting time
UP
0
Setting time
DOWN
0
HOLD.
OFF when power is OFF.
T
POWER
※ RESET
Time limit contact
(⑧-⑥)
Instantaneous contact
(①-③)
Setting time
UP
0
Setting time
DOWN
0
the setting time. Display value will be HOLD.
OFF when power is OFF.
Toff
Ton
POWER
※ RESET
Time limit contact
(⑧-⑥)
Instantaneous contact
(①-③)
Toff
Ton
UP
0
Toff
Ton
DOWN
0
power is ON.
OFF when power is OFF.
Ton
Toff
POWER
※ RESET
Time limit contact
(⑧-⑥)
Instantaneous contact
(①-③)
Toff
Ton
UP
0
Toff
Ton
DOWN
0
power is ON.
OFF when power is OFF.
Rt
T
Rt
T
Toff
Ton
Toff
Ta
Rt
Toff
] mode, timing operation starts with Toff.
Ton
Toff
Ton
Ta
Rt
Ton
] mode, timing operation starts with Ton.
T = Setting time, T > Ta, Rt = Reset time
Operation
T
POWER
Time limit
contact
output
T = set time
T
POWER
Time limit
contact
output
Tout = output time
T = set time
Ton
Toff
Ton
POWER
Time limit
contact
output
Ton, Toff = set time
Enables to set Ton and
Toff time differently.
Toff
Ton
Toff
POWER
Time limit
contact
output
Ton, Toff = set time
Enables to set Ton and
Toff time differently.
T
Tout
T
Toff
Ton
Toff
Ton
Ton
Ton
Toff
Toff