Dynasty VRLA Series Manuale - Pagina 9

Sfoglia online o scarica il pdf Manuale per Camera Accessories Dynasty VRLA Series. Dynasty VRLA Series 19. Valve regulated lead acid battery 20 to 200 ampere-hour capacity

r---
tier/shelf
the total open circuit voltage (OCV) of the
batteries on the tier/shelf
should be verified as:
OCV per Tier = number of batteries per tier X voltage
per battery
If the measured voltage is not as expected, determine
the cause and correct before proceeding.
If a battery is installed with reverse polarity, the
measured voltage for the tier of batteries will be
reduced from the expected value by twice the open
circuit voltage of the individual battery.
Refer to the battery system schematic diagram and
the battery numbers to determine the location of the
various cables interconnecting
the tiers of batteries.
Refer to Tables 2, 3 and 4 for the specific cable to be
used to interconnect
the tiers and rows of batteries
and Figures 7, 8 and 9 for the typical connection
techniques.
Prepare, assemble and secure the intertier cabled
connections
in the same manner as the interunit
cabled connections.
Intertier,
Interrow
and Interrack
Connections
Measure the open circuit voltage of the completely
interconnected
system. The expected voltage
should be:
System OCV = number batteries X battery OCV
Cables used to interconnect
tiers, rows and racks
of batteries should be of at least the same size as the
interunit connecting
cables.
If the measure voltage is not the expected voltage,
determine the cause and correct before proceeding,
r--
Cables supplied as a system meet specific
dimensions
required for racks designed by Dynasty.
This includes consideration
for spacing, maximum load
and cable configuration.
9