Galltec+mela D Series Manuale

Sfoglia online o scarica il pdf Manuale per Accessories Galltec+mela D Series. Galltec+mela D Series 10. Sensors for humidity and temperature measurement with calibrated dmodul

Galltec+mela D Series Manuale
Galltec Mess- und Regeltechnik GmbH
D-71145 Bondorf
Germany
.
Tel. +49 (0)7457-9453-0
Fax +49 (0)7457-3758
.
Technical data
Humidity
measuring element
output range
measuring uncertainty
10...90 %RH
at 10...40°C
< 10 %RH or > 90 %RH at 10...40°C
influence of temperature <10°C or >40°C
Temperature
measuring element
output ranges
fully user configurable via optional USB interface
measuring accuracy
with voltage output at 10...40°C
with current output at 10...40°C
influence of temperature <10°C or >40°C
www.galltec-mela.de
Internet:www.galltec-mela.de
.
capacitive MELA FE09
0...100 %RH
±2 %RH
±2.5 %RH
±0.05 %RH/K
Pt1000 1/3 DIN
0...+50°C
-30...+70°C
0...+100°C
±0.01 K/K
MELA Sensortechnik GmbH
D-07987 Mohlsdorf-Teichwolframsdorf
Tel. +49(0)3661-62704-0
Fax +49(0)3661-62704-20
.
Internet: www.galltec-mela.de
.
D Series
Sensors for
Humidity and Temperature Measurement
With calibrated dModul
Type DW
Industrial version for wall mounting
Optional display
• dynamic MELA ® humidity sensing element
• output of all hx values
• calibrated dModul for
humidity and temperature measurement
• in situ alignment
• easy to install
• operating temperatures up to 80°C
• optional USB interface
The core part of the D Series is the digital calibrated dModul,
which processes the measurement values of relative humidity
and temperature individually. The values are compared to the
calibration values stored in the dModul and communicated
digitally to the transmitter electronics, where they are processed
to standardised current and voltage signals.
The housings of the industrial versions provide protection in ac-
cordance with IP 65. Only a single screw is required to close it
securely.
Electrical data
outputs
voltage supply
consumption of electronics
(voltage output)
load resistance
(voltage output)
load R
L
(current output)
Directive about electromagnetic compatibility 2014/30/EU
DIN EN 61326-1
DIN EN 61326-2-3
±0.2 K
±0.3 K
Germany
.
see type survey
voltage supply - 10 V
R
(Ω)=
L
0,02 A
0...1 V
0...10 V
4...20 mA
typ. 7 mA
≥10 kΩ
±50 Ω
issue 07/13
issue 07/13
Galltec+Mela
D Series_DW
page 1 of 10