AGS Merlin GDP2 Manuale d'uso e installazione - Pagina 6

Sfoglia online o scarica il pdf Manuale d'uso e installazione per Controllore AGS Merlin GDP2. AGS Merlin GDP2 7. Safe area gas detector controller
Anche per AGS Merlin GDP2: Manuale d'uso (12 pagine), Installazione Funzionamento e manutenzione (12 pagine)

AGS Merlin GDP2 Manuale d'uso e installazione
Merlin GDP2
1.
Mains Input 100-240VAC.
2.
Gas Solenoid Valve Power Output, 100-240VAC.
3.
Gas Detector, 24VDC power supply (purchased separately).
4.
Gas Detector, 24VDC power supply (purchased separately).
5.
Remote EM Stop buttons (purchased separately). VOLT FREE INPUT
6.
Fusible Links (purchased separately). VOLT FREE INPUT
7.
Fire panel (Supplied by others). VOLT FREE INPUT
8.
BMS output contacts. Normally Open, Common and Normally Closed..
9.
Sounder Alarm, 24VDC power supply (purchased separately).
10. BMS selection & Auto reset
11. Zone 1 & 2 enable/disable dipswitches.
Rev: 02 Date: 08-01-18

GDP2 Wiring Diagram

Please note, Mains wires and low voltage wires should
not be run in the same conduit as per the
LOW VOLTAGE DIRECTIVE
User & Installation Manual
6