Installation, Operation & Maintenance

Gas Detection Status Information

To access detector status screens, press the 'Gas Detection' section on screen any time.
Switch between pages by touching the relevant page button at the bottom of the screen.
Each page will display up to four ParkSafe detectors:

Detector Status Meaning

GOOD
PRE-ALARM
ALARM
FAULT
END OF LIFE
SERVICE
-- X --

ParkSafe Detector Alarm Set Points

Rising alarm
ppm (Parts per Million)

Modbus Communication Rescan

At any time, the user can rescan and refresh the Modbus communication data if there is a bad connection in
the chain by pressing the icon on screen.
When pressed the system will search for all signals connected to the controller i.e., gas detectors
without the need to reset the system.
Rev: 20
To return to the main screen, press the home button on screen.
Gas levels are safe / No error conditions.
o
Gas detected has reached pre-alarm levels.
o
Gas detected has reached alarm levels.
o
Gas sensor module has an issue (Removed or not properly installed).
o
The gas-sensing element has reached the end of its expected lifecycle.
o
Gas sensing element requires annual periodic bump test.
o
Detector signal lost, not installed or not configured correctly.
o
Detector Type
Carbon Monoxide (CO)
Nitrogen Dioxide (NO2)
The ID configured via switches on each detector board.
a.
The unique serial number for that detector.
b.
The target gas that detector is monitoring.
c.
The status of gas levels, errors, and messages.
d.
The concentration value of gas detected.
e.
Pre-Alarm
▲ 25ppm
▲ 0.7ppm
ParkSafe Controller
Alarm
▲ 100ppm
▲ 2.0ppm
12