Galvin Engineering CliniLever TCWTC150HC Installazione del prodotto Manualline - Pagina 4

Sfoglia online o scarica il pdf Installazione del prodotto Manualline per Apparecchiature per il bagno Galvin Engineering CliniLever TCWTC150HC. Galvin Engineering CliniLever TCWTC150HC 4. Cp-bs hospital wall top assembly

Product Installation Guidelines
SERVICE AND MAINTENANCE
JUMPER VALVE TAPWARE
1. Turn off the water supply and turn on the tap
handle to drain water from the bodies.
2. Remove the temperature indicator from the
handle.
3. Remove the handle from the tap.
4. Unscrew the top assembly from the body.
5. Check the o-ring on the spindle and the jumper
valve for wear and damage. Replace if required.
6. Clean the spindle and body of debris.
7. Place a new o-ring (if required) onto the spindle
and re-grease with potable water approved
grease.
8. Re-assemble top assembly. Follow the product
installation guidelines for the relevant product
re-assembly method.
WARRANTY
The warranty set forth herein is given expressly and is the only warranty given by the Galvin Engineering Pty Ltd.
With respect to the product, Galvin Engineering Pty Ltd makes no other warranties, express or implied. Galvin
Engineering Pty. Ltd. hereby specifically disclaims all other warranties, express or implied, including but not limited to
the implied warranties of merchantability and fitness for a particular purpose.
Galvin Engineering Pty Ltd products are covered under our manufacturer's warranty available for download from
www.galvinengineering.com.au Galvin Engineering Pty Ltd expressly warrants that the product is free from
operational defects in workmanship and materials for the warranty period as shown on the schedule in the
manufacturer's warranty. During the warranty period, Galvin Engineering will replace or repair any defective products
manufactured by Galvin Engineering without charge, so long as the terms of the Manufacturer's warranty are
complied with.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for
breach of warranty, and Galvin Engineering Pty Ltd shall not be responsible for any incidental, special or
consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property
which is damaged if this product does not work properly, other costs resulting from labour charges, delays,
vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical,
electrical or any other circumstances over which Galvin Engineering has no control. This warranty shall be
invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the
product.
© Galvin Engineering Pty Ltd
Version 1, 4 November 2022, Page 4
CERAMIC CARTRIDGE TAPWARE
1. Turn off the water supply and turn on the tap
handle to drain water from the bodies.
2. Remove the temperature indicator from the
handle.
3. Remove the handle from the tap.
4. Unscrew the ceramic head part from the body.
5. Check the o-ring on the ceramic head part for
wear and damage. Replace if required.
6. Clean the head part and the body of any debris.
7. Replace the cartridge and hand tighten back into
the body.
8. Follow the product installation guidelines for the
relevant product re-assembly method.
Document No.: 001.00.10.18
Version 1, 4 November 2022, Page 4 of 4
of 4