MINI MERLIN LPGCO
8.
Power On & Off
How to turn your device ON
 Supply 110-120vAC mains to the [POWER/ LINE IN] terminal.
 Press and hold the touch button on the front of the unit for 3 seconds.
 After initial warm up, the screen will show both LPG and CO levels in the area.
 Remove or Switch Off the mains power supply.
9.

Building Management System Integration

This device can be integrated with a Building Management System (BMS), a home alarm
system, or be used as part of a boiler low voltage safety limit to make or break a circuit on
both gases separately, (valve open or valve closed) depending on the system.
These switches can be used for a variety of purposes including triggering alarm contacts,
operating and external relay for multiple appliance shut-down and generating status signals
for a BMS system.
10.

Wiring Applications

Gas Supply Controlled by ~120vAC Solenoid Valve
CAUTION: If you use a gas solenoid valve, please note that
standing pilots will need to be re-lit. We do not recommend
installing a gas solenoid valve with standing pilots.
Gas Supply Controlled by 24vAC Solenoid Valve
When the GAS VALVE terminal is wired to a normally closed
(NC) gas solenoid valve, the device can be used to isolate
gas supply for multiple appliances.
The diagram shown opposite uses an external transformer
(not supplied) to close a 24vAC gas solenoid valve that
could supply gas to one or more appliances.
CAUTION: If you use a gas solenoid valve, please note
that standing pilots will need to be re-lit.
We do not recommend installing a gas solenoid valve with
standing pilots.
Rev: 03 05-19
USER GUIDE
10