AGS Merlin 500S+ Manuale d'uso - Pagina 3

Sfoglia online o scarica il pdf Manuale d'uso per Pannello di controllo AGS Merlin 500S+. AGS Merlin 500S+ 8. Two zone isolation panel

Merlin 500S+
1

General Information

The Merlin 500S+ is a two zone isolation panel with two outputs: UTILITY 1 & UTILITY 2.
The 500S+ is designed to provide an effective way of isolating gas, water, electricity or oil etc.
by means of a key switch on the panel or by the operation of the emergency shut off button.
The 500S+ can be integrated with a BMS, fire alarm and remote emergency shut-off buttons.
It is recommended that the user reads this guide before using the system.
Please do NOT attempt to operate the unit until the contents of this document have been read
and are thoroughly understood.
Panel Mounting
The control panel is designed for surface mounting using 4 mounting screws (not supplied).
Removing the cover on the panel gives access to the mounting holes and circuit board.
2

Installation

2.1

Mains Line Supply

A 110-120VAC single phase electrical supply should be supplied to the
panel.
This should be externally fused at 3 Amps using a fuse or circuit
breaker.
2.4

Remote Emergency Shut Off Buttons

The terminal for remote emergency shut-off buttons is detailed on the circuit
board as [EM REMOTE].
These connections are linked out as a factory setting.
Remote emergency shut-off buttons should be volt free and wired to the
Merlin 500S+ using a plenum security cable. White, 18/2 (18AWG 2 conductor),
stranded, CMP or similar.
Rev: 04 Date: 04-03-19
2.2

Utility 1

The UTILITY should be powered using the terminals on
the Merlin 500S+ marked [LNE UTILITY 1].
2.3

Utility 2

The UTILITY should be powered using the terminals on the
Merlin 500S+ marked [LNE UTILITY 2].
User Guide
3