Jacuzzi 27843.01 Manuale di installazione e funzionamento - Pagina 5
Sfoglia online o scarica il pdf Manuale di installazione e funzionamento per Filtro per piscina Jacuzzi 27843.01. Jacuzzi 27843.01 19. Domestic chlorine generating device
Section 1b – GENERAL PRODUCT INFORMATION
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
INSTALLATION AND EQUIPMENT RELATED
When installing and using your Commander III Model JC13Control Box, basic safety precautions must
always be followed, including the following:
1. Follow all aspects of the local and National Electrical Code(s) when installing your Control Box.
2. During installation, mount your Control Box to ensure the least amount of direct exposure to rain, garden sprinkler water,
direct sunlight or any corrosive environment.
3.
DANGER – Risk of electrical shock. Install Control Box at least 3 m (10 ft.) for 115VAC Units, from the inside wall
of the pool or spa using non-metallic plumbing. 1.5 m (5 ft.) minimum distance for 230VAC Units.
4. All field-installed metal components such as rails, ladders, drains or similar hardware within 3 m (10 ft.) of the spa or hot
tub shall be bonded to the equipment grounding bus with copper conductors not smaller than 8.4 mm² (No. 8 AWG) in the
U.S.A. and 6.3mm² (No. 6 AWG) in Canada.
5.
WARNING – Maintain water chemistry in accordance with manufacturer's instructions.
6.
DANGER – To reduce the risk of injury, do not permit children to use this product unless they are closely supervised
at all times. Children should not use spas, hot tubs or pools without permanent adult supervision.
1
A wire connector is provided on your Commander III Model JC13 to connect a minimum 8.4 mm² (No. 8 AWG) in the
U.S.A. and 6.3mm² (No.6 AWG) in Canada solid copper bonding conductor between this unit and any metal equipment,
metal enclosures of electrical equipment, metal water pipe or conduit within 1.5 m (5 ft.) of the unit.
2
A bonding terminal is located inside your Commander III Model JC13. To reduce the risk of electrical shock, this
terminal must be connected to the grounding means provided in the electrical supply panel with a continuous copper wire
equivalent size to the circuit conductors supplying your Commander III Model JC13.
3
A disconnection device from the power source, with a contact separation of at least 3mm (0.12 in.) in all poles, must be
incorporated in the fixed wiring for permanently wired units.
4
The input voltage to the Commander III Model JC13 must match the 115/230VAC jumper terminals on the Circuit board,
marked "TRANSFORMER PRIMARY", shown on Page 4.
Installation of all Commander III models:
Equipment Related
115/230VAC, 50/60 Hz Models (fixed wiring)
SAVE THESE INSTRUCTIONS
2