ELECTRICAL CONNECTION
The oven must be electrically grounded in accordance with all local and national codes (in the USA, the National
Electrical code ANSI/NFPA no. 70 is applicable).
PHASE CONVERSION INSTRUCTIONS
Please follow the below steps to convert the phase of your oven to match your application.
NOTE: Only phase can be converted. The voltage of these ovens cannot be converted.
Please ensure that your oven is the proper voltage to be used with your electrical connection.
Convert 3 phase to 1 phase
1. Remove wires 'a' , 'B' , 'b' , and 'C,' from their
terminal block locations
2. Secure wires ' A ' , 'B' , and 'C,' to the same
terminal block location
3. Secure wires 'a' , 'b' , and 'c,' to the same
terminal block location
Reference image above
6
3 Phase
User Manual
1 Phase
Convert 1 phase to 3 phase
1. Remove wires 'a' , 'B' , 'b' , 'C,' from their
terminal block locations
2. Secure wires ' A ,' and 'a,' to the same terminal
3. Secure wires 'B,' and 'b,' to the same terminal
block location
4. Secure wires 'C,' and 'c,' to the same terminal
block location
Reference image above