ADF ADH100ID Istruzioni per il supplemento - Pagina 8
Sfoglia online o scarica il pdf Istruzioni per il supplemento per Camino da interno ADF ADH100ID. ADF ADH100ID 17. Double sided inbuilt heater zero clearance box
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
If ceiling is Raked solid ceiling, or Capped heater cavity
• This option is with heater cavity built up to a raked ceiling (i.e. sandwich roof
construction), or the cavity is capped in the room; the cavity must be vented.
See 3.4.2.2 in AS2918:2018 for options for water proofing and to ensure venting
through roof.
• Include top and bottom vents, Minimum area 400mm x 50mm open air space
vents.
• Top and Bottom vents can be swapped to Front of the Chimney breast build-out,
if including cabinetry on both sides.
NOTE: Wall Vents not supplied, ie choose vents to match décor.
Cowl
Casing cover
Flue pipe
Inner casing
600 mm min.
Outer casing Venting casing
25 mm air gap for venting Spigot metal f lashing
Non- combustible chase capping
1/11/19
Vent Roof opening as per
3.4.2.2 in AS2918:2018
8