ADF LINEA 100 Manuale di istruzioni per il montaggio - Pagina 3
Sfoglia online o scarica il pdf Manuale di istruzioni per il montaggio per Camino da interno ADF LINEA 100. ADF LINEA 100 16. Nmv inbuilt heater zero clearance box supplement instructions
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Dimensions for Build out (Front elevation):
• The hearth beneath the unit must include 6mm cement sheet to 1275mm x
550mm deep. The hearth in front of the unit must include 6mm cement
sheet with minimum 1420mm x 600mm deep.
• No combustibles within 300mm from the top of the Zero Clearance box (i.e.
to first noggin), 100mm to each side (stud) and 50mm from the rear. No
combustible material to be used in construction at all in this cavity space.
• Fan cable must be below the level of the heater base and exit the cavity
below the level of the heater.
1275mm
100mm
1420mm
100mm
300mm
1/1/21
1375mm
3