CORNING EDGE-10U-PRH Manuale di avvio rapido - Pagina 6

Sfoglia online o scarica il pdf Manuale di avvio rapido per Involucro CORNING EDGE-10U-PRH. CORNING EDGE-10U-PRH 8. Edge port replication housing

Step 3: Mate the MTP connector into the adapter at the rear of the module.
NOTE:
When using the panel, you will install MTP trunks into the EDGE™ or EDGE8® modules. Figure 11 shows the
EDGE modules MTP mating; EDGE8 modules are installed in the same manner.
TPA-4785-B
9.
(OPTIONAL) Install CDF Bracket
An optional CDF bracket may be installed external to the housing on the frame to provide additional cable trunk
installation positions. It supports incoming cable installation from the top or bottom of the frame into the housing.
The bracket is available in three sizes:
EDGE-CDF-RJ04-BKT — 4-position furcation trunk holder
EDGE-CDF-RJ08-BKT — 8-position furcation trunk holder
EDGE-CDF-RJ12-BKT — 12-position furcation trunk holder
Step 1:
Position CDF bracket for optimized leg reach and routing.
Step 2:
Install bracket using two 12-24 screws (Figure 12)). Allow enough clearance when routing trunks from the
bracket into the housing to ensure bend radius is maintained when trunks enter the housing.
Step 3:
Insert furcation plug into cradle as seen in Section 6 and mount cradle onto CDF bracket (Figure 8).
Step 4:
Remove appropriate cable entry cover as described in Section 6. Then route trunks inside the housing
through the openings and terminate at the back of the module.
TPA-4786
Standard Recommended Procedure 003-991-AEN | Issue 5 | January 2021 | Page 6 of 8