3.10
Installing Preconnectorized Cable into Connector Modules (Plug & Play™)
Step 1:
Using a 6-32 hex nut driver, remove the radius control guides. (This is recommended
when cables enter from the right side of the housing.)
Step 2:
Reinstall the nuts onto the radius guide studs to prevent fiber snags.
Step 3:
Remove the blank panels from the unit and replace with connector modules (purchased
separately).
Step 4:
Install MTP connectors into the MTP adapters at the rear of the connector modules
(Figure 10). Route fiber as shown and loosely secure with cable ties.
IMPORTANT:
STANDARD RECOMMENDED PROCEDURE 003-649 | ISSUE 5 | JANUARY 2009 | PAGE 8 OF 10
Lift the tray stop latches and slide the drawer to the forward and back positions to
verify that the drawer slides in the grooves of the guides and that there is enough
fiber slack to prevent violating the minimum fiber bend radius of the cable.
Cable Tie
KPA-2226
Figure 9 — Fiber Routing to External Splice Housing
Cable Tie
KPA-2245
Figure 10 — Install Plug & Play Modules