KitchenAid 30" Istruzioni per l'installazione - Pagina 3
Sfoglia online o scarica il pdf Istruzioni per l'installazione per Cappa di ventilazione KitchenAid 30". KitchenAid 30" 8.
B. Electrical requirements
WARNING:
DO NOT PLUG THE "PIGTAIL'
POWER CORD INTO A LIVE WALL RECEPTACLE
BEFORE CORD IS PERMANENTLY
CONNECTED
TO THE TERMINAL
BLOCK.
1
2.
3.
4.
5.
This appliance
must be connected
to the proper
electrical voltage and frequency
as specified on
nameplate.
A separate 40 ampere circuit is
required. Fuse both sides of the line. DO NOT
fuse the neutral. A time-delay
fuse or circuit
breaker is recommended.
Wire sizes must
conform to the requirements
of the National
Electrical Code ANSI/NFPA
70-l 984 and/or local
codes and ordinances.
The nameplate
is located
on the front frame of the oven behind the door.
All wires ending at the appliance
must terminate
in ring type terminals.
All power cords and cables to appliance
must be
fitted with a UL approved strain relief.
The range should be connected
with copper wire
only. Aluminum
wire requires special connectors.
Improper use may create a fire hazard.
Appliance
may be connected
directly to the fused
disconnect
(or circuit breaker) box through flexible
armored or non-metallic
sheathed
copper cable.
Do not use an extension
cord. Allow 4 feet (min.)
slack so appliance
can be moved for servicing.
Wire sizes must conform to the ampere rating of
the range. See paragraph
B-l above.
6.
WARNING:
THE TERMINAL
BLOCK ON THE
APPLIANCE
ACCEPTS
COPPER WIRE ONLY,
NOT ALUMINUM.
IF ALUMINUM
HOUSE
WIRING MUST BE CONNECTED,
USE ONE OF
THE FOLLOWING
PROCEDURES:
l
Connect copper wire to the range terminal
block (use ring terminals).
l
Attach special ring connectors
to the
aluminum
house wiring that are UL listed
and designed for joining copper to
aluminum.
These special ring connectors
(available at electrical supply houses) can be
attached directly to the range terminal block.
l
The connectors
must conform to the ampere
rating of the range as stated in paragraph
B-i.
7. If local codes permit, your range may be
connected
with a three wire flexible type, UL listed
"pigtail"
power cord of the proper ampere rating?
Plug must match a 3-wire NEMA type lo-50R
receptacle
(shown below).
3-wire
receptacle
lo-50R
8.
CAUTION:
FOR MOBILE HOME USE, A 4-WIRE
POWER CORD MUST BE USED. This appliance
is manufactured
with ground connected
to frame.
This must be revised so green grounding
wire of 4-
wire power cord is connected
to frame.
If using a 4-wire NEMA type 14-50R receptacle
(shown above) you must use a matching 4-wire
UL listed "pigtail"
power cord. Cord should be
type SRD or SRDT, at least 4 feet long with all
conductors
ending in ring terminals
at the
appliance.
MINIMUM
CONDUCTOR
SIZE..
(4-WIRE COPPER POWER CORD)
For 40 ampere circuits: two No. 8 conductors,
one
No. 10 white neutral, and one No. 8 green ground.
*CAUTION:
Power Cord Requirements-Only
a power supply cord kit rated at 240 volts, 50
amperes and investigated
for use with ranges
shall be used.
3