Fujitsu SPARC Enterprise T5120 Manuale di pianificazione del sito - Pagina 23
Sfoglia online o scarica il pdf Manuale di pianificazione del sito per Server Fujitsu SPARC Enterprise T5120. Fujitsu SPARC Enterprise T5120 26. Sparc enterprise
Anche per Fujitsu SPARC Enterprise T5120: Panoramica del manuale (34 pagine), Manuale introduttivo (12 pagine), Manuale introduttivo (12 pagine), Manuale di sicurezza e conformità (34 pagine)
Related Information
"Ambient Relative Humidity" on page 10
■
Airflow Considerations
Ensure unobstructed airflow through the chassis.
■
Ensure that inlet air enters at the front of the server and exits from the back.
■
Ensure that the server ventilation openings used for intake and outflow of air
■
provide an open area that is at least 60% of the open area perforations across the
front and rear of the server. This 60% minimum open area equates to the following
dimensions, depending on the server model:
Minimum Open Area
SPARC Enterprise T5120 Server
SPARC Enterprise T5220 Server
Allow a minimum of 5 mm (0.2 in) clearance at the front of the system and 80 mm
■
(3.1 in) at the rear of the server when mounted. These clearance values are based
on the preceding inlet and exhaust impedance (available open area) and assume a
uniform distribution of the open area across the inlet and exhaust areas. Clearance
values greater than these are recommended for improved cooling performance.
Note – The combination of inlet and exhaust restrictions such as cabinet doors and
the spacing of the server from the doors can affect the cooling performance of the
server and should be evaluated by the user.
Take care to prevent recirculation of exhaust air within a rack or cabinet.
■
Manage cables to minimize interfering with the server exhaust vent.
■
Related Information
SPARC Enterprise T5120 and T5220 Servers Overview Guide
■
SPARC Enterprise T5120 and T5220 Servers Getting Started Guide
■
SPARC Enterprise T5120 and T5220 Servers Getting Started Guide (DC)
■
Metric Units
2
112.2 cm
(425 mm x 44 mm)
2
224.4 cm
(425 mm x 88 mm)
SPARC Enterprise T5120 and T5220 Servers Site Planning Guide
US Units
2
17.4 in
(16.7 in x 1.7 in)
2
34.8 in
(16.7 in x 3.5 in)
11