Indesit KD341GW Manuale di istruzioni per l'installazione e l'uso - Pagina 17
Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione e l'uso per Fornelli Indesit KD341GW. Indesit KD341GW 24. 50cm gas cooker
Installation Instructions
Prior to installation, ensure that the local distributions (nature of the gas and gas
pressure) and the adjustment conditions are compatible. The adjustment conditions
for this appliance are stated on the data badge which is fitted on the outer rear panel
of the cooker. This appliance is not designed to be connected to a combustion prod-
ucts evacuation device. It must be installed and connected in accordance with current
installation regulations. Particular attention should be given to the relevant require-
ments regarding ventilation.
MODEL KD341G
Category I2H (G.B. IE)
This model is set to burn NATURAL GAS (G20) at 20 mbar ONLY and cannot be used on
any other gas.
GAS SAFETY (INSTALLATION & USE) REGULATIONS
It is the law that all gas appliances are installed by competent persons in accordance
with the current edition of the above regulations. It is in your interest and that of safety
to ensure compliance with the law.
In the UK, CORGI registered installers work to safe standards of practice.
The cooker must also be installed in accordance with BS 6172.
Failure to install the cooker correctly could invalidate the warrantY liability claims and
could lead to prosecution.
LOCATION
The cooker may be located in a kitchen, kitchen/diner or a bed-sitting room, but not in
a room containing a bath or shower. The cooker must not be installed in a bed-sitting
room of less than 20m
3
.
PROVISION FOR VENTILATION
The room containing the cooker should have an air supply in accordance with
BS 5440: Part 2
The room must have an opening window or equivalent; some rooms may also require
a permanent vent. If the room has a volume between 5 and 10m
3
, it will require an air
vent of 50cm
2
effective area unless it has a door which opens directly to outside. If the
room has a volume of less than 5m
3
, it will require an air vent of 100cm
2
effective area.
If there are other fuel burning appliances in the same room, BS 5440: Part 2 should be
consulted to determine air vent requirements.
17