A-Neutronics MS-1917-LCD Manuale di istruzioni - Pagina 5

Sfoglia online o scarica il pdf Manuale di istruzioni per Unità di distribuzione dell'alimentazione A-Neutronics MS-1917-LCD. A-Neutronics MS-1917-LCD 8. 17 outlet 19in rack mount w/ lcd display

LCD DISPLAY METER FUNCTION
METER FUNCTION
OVER VOLTAGE AND OVER CURRENT WARNING
1. LCD display will show "OUP" when the input voltage is over 145V.
2. LCD display will "blink" when the input current is over 15A.
FUNCTION
RANGE
Volts
95.0~125 Vrms
Amps
0.00~15.0 Amps
Watts
1875 Watt
VA
1875 VA
Frequency
47.0~63.0Hz
Power Factor
0.00~1.00
KWh
0.00~9999
KWh hour
0.00~9999
(8) FUNCTIONS PROVIDED
Plug in the power strip and it starts to display current power supply status.
Voltage
Amp
Watt
VA
Hz
PF
Kwh
Runtime Clock
No start button required. FUNCTION and SET buttons are located on the right side of the
LCD Display.
OPERATION
1. Plug in the strip, the display will show voltage reading.
2. Press "FNC" button, to show amperage reading.
3. Press "FNC" button again, to show watt reading.
4. Press "FNC" button again, to show VA (apparent power) reading.
5. Press "FNC" button again, to show Hz (frequency) reading.
6. Press "FNC" button again, to show PF (power factor) reading.
7. Press "FNC" button again, to show KWH (kilo watt per hour) reading.
8. Press "FNC" again, to show runtime (clock).
RE-SET KWH AND CLOCK
Press "SET" button for about 3 seconds at KWH or clock mode to reset the KWH and clock.
NOTE: Pressing "SET" in any other mode brings up a menu that permits the base value
of the power strip to change.The range is 1-30 Amps incrementally. This should never
be changed!! This power strip is designed to operate at 15Amps and changing the value
will only give incorrect meter readings. Changing the value does not allow more then the
specified amperage on the label.
ACCURACY
0.2%
0.3%
0.5%
0.5%
+/- 0.1Hz
0.01%
.5%
30ppm
3