Kohler Various Bollettino di servizio - Pagina 2

Sfoglia online o scarica il pdf Bollettino di servizio per Motore Kohler Various. Kohler Various 3.

Kohler Various Bollettino di servizio
Test meter leads before use. (Set meter to Ohms and check for resistance reading of less than 0.5 Ohm.)
If available, use clamping meter leads to assist with testing.
Set meter to next highest voltage scale that includes 12 VDC.
When taking readings, allow the meter to stabilize before recording. The reading should stabilize after 3 to 5
seconds. If reading continues to drop while cranking, stop the test and perform a battery load test.
Solenoid Shift Starter Warranty Test Procedures
Test #1
Battery Voltage Test (Static)
DVOM
+
-
+
Battery
Test 1 Conclusions
If battery voltage is above 12.4
VDC continue to Test 2.
If voltage is below 12.4 VDC,
charge battery and retest.
If battery will not hold a charge
it should be replaced before
continuing the test or replacing
the starter.
Voltage Drop Across Battery (Cranking)
NOTE: Touch meter
leads to actual battery
terminals.
-
VDC
Test 2 Conclusions
If battery cranking voltage is
above 9.0 VDC continue to
Test 3.
If battery cranking voltage is
below 9.0 VDC you should
check the battery by using
a load tester. Also check for
external engine load.
Test #2
DVOM
+
-
NOTE: Use starter
end plate as test
+
-
Battery
VDC
Test 3 Conclusions
2
Test #3
Voltage Drop Across Starter (Cranking)
DVOM
+
-
point.
+
Starter
-
VDC
If the difference between test
2 and test 3 is greater than 1
VDC check all positive and
negative electrical connections
for corrosion and/or loose
fasteners in the starter circuit.
If additional starter testing
is necessary, refer to proper
service manual for complete
troubleshooting information.