Kohler 14RESA Istruzioni per l'installazione - Pagina 2

Sfoglia online o scarica il pdf Istruzioni per l'installazione per Generatore portatile Kohler 14RESA. Kohler 14RESA 4. Residential/commercial generator sets
Anche per Kohler 14RESA: Manuale di risoluzione dei problemi (8 pagine), Istruzioni per l'installazione (2 pagine), Funzionamento (20 pagine), Manuale di istruzioni per l'installazione e il funzionamento (37 pagine)

Kohler 14RESA Istruzioni per l'installazione
Alternator Specifications
Specifications
Manufacturer
Output reconnectable
Type
Leads, quantity
Voltage regulator
Insulation:
Material
Temperature rise
Bearing: quantity, type
Coupling
Amortisseur windings
Voltage regulation, no-load to full-load
RMS
One-step load acceptance
Peak motor starting kVA @ 240 V:
14RESA
20RESA
Engine
Engine Specifications
Manufacturer
Engine: model, type
Cylinder arrangement
3
Displacement, cm
(cu. in.)
Bore and stroke, mm (in.)
Compression ratio
Main bearings: quantity, type
Rated RPM
60 Hz
50 Hz
Max. engine power at rated rpm, kW (HP)
LP vapor, 60 Hz
LP vapor, 50 Hz
Natural gas, 60 Hz
Natural gas, 50 Hz
Cylinder head material
Valve material
Piston type and material
Crankshaft material
Governor: type
Frequency regulation, no load to full load
Frequency regulation, steady state
Air cleaner type
Exhaust
Exhaust System
Exhaust temperature exiting the
enclosure at rated kW, dry, _C (_F)
Alternator Specifications
PowerBoostt Generator
1-Phase
Kohler
120/240
2-Pole, Rotating Field
4
Digital
NEMA MG1-1.66
Class H
Class H
1, Sealed Ball
Direct
Full
±0.5%
100% of Rating
35
40.5
Application Data
14RESA
20RESA
Kohler
CH740
CH1000
4-Cycle
4-Cycle
V-2
725 (44)
999 (61)
83 x 67
90 x 78.5
(3.27 x 2.64)
(3.54 x 3.1)
9:1
8.8:1
2, Parent Material
3600
3000
17.6 (23.6)
23.0 (30.9)
15.8 (21.2)
20.0 (26.8)
15.3 (20.5)
20.2 (27.1)
13.8 (18.5)
16.8 (22.5)
Aluminum
Steel/Stelliter
Aluminum Alloy
Heat Treated, Ductile Iron
Electronic
Isochronous
±0.5%
Dry
14RESA
20RESA
260 (500)
G4-209 (14/20RESA) 12/11
Alternator Features
D
Compliance with NEMA, IEEE, and ANSI standards for
temperature rise
D
Self-ventilated and dripproof construction
D
Vacuum-impregnated windings with fungus-resistant
epoxy varnish for dependability and long life
D
Superior voltage waveform and minimum harmonic
distortion from skewed alternator construction
Digital voltage regulator with ±1.5% no-load to full-load
D
RMS regulation
D
Rotating-field alternator with static exciter for excellent
load response
D
Skewed generator construction produces a smooth
AC waveform
Engine Electrical
Engine Electrical System
Ignition system
Starter motor rated voltage (DC)
Battery (purchased separately):
Ground
Volts (DC)
Battery quantity
Recommended cold cranking amps:
(CCA) rating for --18_C (0_F)
Group size
Lubrication
Lubricating System
Type
Oil capacity (with filter), L (qt.)
Oil filter: quantity, type
Oil cooler
Fuel Pipe Size
Minimum Gas Pipe Size Recommendation, in. NPT
14RESA
Natural
Gas
Pipe
193,000
Length,
Btu/hr.
m (ft.)
8 (25)
3/4
15 (50)
1
30 (100)
1
46 (150)
1 1/4
61 (200)
1 1/4
14RESA
20RESA
Electronic,
Capacitive Discharge
12
Negative
12
1
500
51
14RESA
20RESA
Full Pressure
1.9 (2.0)
2.8 (3.0)
1, Cartridge
Integral
20RESA
Natural
LP Vapor
Gas
LP Vapor
203,000
281,000
340,000
Btu/hr.
Btu/hr.
3/4
1
3/4
1
1
1 1/4
1
1 1/4
1
1 1/4
Btu/hr.
3/4
1
1
1 1/4
1 1/4