Kohler 15REYG Funzionamento - Pagina 19

Sfoglia online o scarica il pdf Funzionamento per Generatore portatile Kohler 15REYG. Kohler 15REYG 40. Commercial generator sets

Kohler 15REYG Funzionamento
2.3.5
Resetting Controller after a Fault
Shutdown
Always identify and correct the cause of a fault
shutdown before resetting the controller.
following procedure to reset the generator set controller
after a fault shutdown.
1. Move the generator set master switch to the
OFF/RESET position.
2. Disconnect the generator set from the load using
the line circuit breaker or ATS. See the safety
precautions at the beginning of this manual before
proceeding.
3. Identify and correct the cause of the fault
shutdown.
See the safety precautions at the
beginning of this manual before proceeding. Refer
to Section 4, Troubleshooting.
4. Start the generator set by moving the generator set
master switch to RUN. Test operate the generator
set to verify that the cause of the shutdown has
been corrected.
5. Shut the generator off by moving the generator set
master switch to the OFF/RESET position.
6. Reconnect the generator set to the load using the
line circuit breaker or ATS.
7. Move the generator set master switch to the AUTO
position for startup by remote transfer switch,
remote start/stop switch, or remote digital gauge.
Note: Opening and closing the remote start/stop
contact also resets the controller. Always identify
and correct the cause of the fault shutdown
before restarting the generator set.
TP-6728 10/11
2.3.6
The ADC 2100 is powered by the generator set engine
starting battery.
Use the
When the generator set master switch is in the AUTO
position, the controller may power down after a period of
inactivity. The controller's communication parameter
(Cn) setting determines the power down mode. See the
generator set installation manual for controller
configuration information.
48-hour power down (default setting).
ADC 2100 communication parameter is set to Cn00, the
controller automatically powers down after 48 hours of
inactivity. A remote start signal (from a transfer switch or
a remote start/stop switch connected to P21 connector,
leads 3 and 4) or moving the generator set master switch
to the RUN position turns the controller back on.
Continuous power mode.
communication parameter is set to Cn01, the controller
will not power down. The controller remains powered at
all times to maintain CANbus communication and to
allow remote start commands from a remote CAN
gauge. A battery charger is recommended to maintain
the engine starting battery.
Note: The ADC 2100 draws 250 mA when the master
switch is in the AUTO position and the unit is
configured for CAN communication.
1-hour power down.
parameter to Cn06 will cause the controller to power
down after 1 hour of inactivity. In this mode, a remote
digital gauge using CAN communication will not be able
to activate the controller after power down. A remote
start signal (from a transfer switch or a remote start/stop
switch connected to P21 connector, leads 3 and 4) or
moving the generator set master switch to the RUN
position turns the controller back on.
application code version 1.21 or higher is required for
the 1-hour power down option.

Controller Power Down

Setting the communications
Section 2 Operation
If the
If the ADC 2100
Controller
19