Kohler 18RESNT Funzionamento - Pagina 30

Sfoglia online o scarica il pdf Funzionamento per Generatore portatile Kohler 18RESNT. Kohler 18RESNT 48. Residential/commercial generator sets
Anche per Kohler 18RESNT: Manuale di installazione (40 pagine)

Kohler 18RESNT Funzionamento
Clean the battery and cables and tighten battery
terminals using the service schedule recommendations.
To prevent corrosion, maintain tight, dry electrical
connections at the battery terminals.
corrosion from battery terminals, disconnect the cables
from the battery and scrub the terminals with a wire
brush. Clean the battery and cables with a solution of
baking soda and water. After cleaning, flush the battery
and cables with clean water and wipe them with a dry,
lint-free cloth.
After reconnecting the battery cables, coat the battery
terminals with petroleum jelly, silicone grease, or other
nonconductive grease.

3.9 Battery Charger

The generator set is equipped with a 6-amp
float/equalize battery charger to maintain the engine
starting battery. The charger's DC leads are factory-
wired. Figure 3-9 illustrates the battery charger.
Periodically tighten all connections.
maintenance on the battery charger is required.
1
2
INDICATOR
Red:
VOLTS= 11.8- -14.0
AMPS= 5.0- -6.0
Red & Green:
VOLTS= 14.0- -14.5
AMPS= 1.5- -5.0
Green:
VOLTS= 13.0- -13.6
AMPS= 0.1- -1.5
CAUTION:
To reduce the risk of elect rical shock,
connect only to properly gr ounded outlet.
INPUT: 115 VAC 50/60Hz @ 1.6A
OUTPUT: 12 VDC @ 6 Amps
MAX. BAT.: 180 Amp Hr. Max.
DATE:
Allowable Battery Types: Lead Acid a
5
4
1. LED indicators
2. Mounting flanges
3. AC power cord
Figure 3-9 6-Amp Float/Equalize Battery Charger
30
Section 3 Scheduled Maintenance, 12 kW Models
To remove
No other
2
6 AMP AUTOMATIC
BATTERY CHARGER
R
C
US LISTED
BATTERY CHARGER
53AB
2608KH
nd Gel Cell
3
4. Fuse
5. Battery leads, 12 VDC

3.10 Circuit Protection

If the generator set circuit breaker trips or the fuses blow
repeatedly, see Section 5, Troubleshooting, for possible
causes.

3.10.1 Line Circuit Breaker

A line circuit breaker interrupts the generator output in
the event of a fault in the wiring between the generator
and the load. The line circuit breaker location is shown
in Figure 1-1. The circuit breaker rating is 50 amps. If
the circuit breaker trips, reduce the load and switch the
breaker back to the ON position. With the breaker in the
OFF position, the generator set runs but the generator
output is disconnected from the load.

3.10.2 Fuses

Two 10-amp and one 20-amp inline fuse are mounted
on the controller junction box. See Figure 3-10. Another
10-amp fuse is located in the battery charger lead.
Always identify and correct the cause of a blown fuse
before restarting the generator set. Refer to Section 5,
Troubleshooting, for conditions that may indicate a
blown fuse.
Replace blown fuses with identical
replacement parts.
Fuse
Auxiliary winding, 20 A
Relay interface board, 10 A
Controller, 10 A
Battery charger, 10 A
Figure 3-10 Fuses
Label
Part Number
F1
292937
F2
223316
F3
223316
223316
TP-6517 4/09