AB Quality GuardPLC 1800 Manuale di istruzioni per l'installazione - Pagina 12
Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione per Controllore AB Quality GuardPLC 1800. AB Quality GuardPLC 1800 20.
12
GuardPLC™ 1600 Controllers
Terminal Number
31
32
33
34
35
36
37
38
39
40
41
42
LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only it's four
related inputs.
Line Control
Line control is a short-circuit and line break monitoring system (e.g., E-Stop inputs)
which can be configured for the GuardPLC system. Up to 8 digital outputs (DO1 to
DO8) can be configured as pulsed outputs. The example below shows 2 pulse
outputs connected to the digital inputs (DI) of the same system. As a result, the
connections to the digital inputs (DI) are monitored.
Emergency OFF 1
Publication 1753-IN001B-EN-P - March 2004
Designation
LS+
13
14
15
16
L-
LS+
17
18
19
20
L-
DO 1
2
DI 1
2
DI 3
Function
Sensor supply for inputs 13 to 16
Digital input13
Digital input 14
Digital input 15
Digital input 16
Reference pole
Sensor supply for inputs 17 to 20
Digital input 17
Digital input 18
Digital input 19
Digital input 20
Reference pole
Emergency OFF 2
4