Error code
Description
Grid frequency out of range
1. Check the frequency is in the range of specification or not;
F48
AC lower frequency
2. Check whether AC cables are firmly and correctly connected;
3. Seek help from us, if can not go back to normal state.
Battery voltage low
1. Check whether battery voltage is too low;
DC busbar voltage is
F56
2. If the battery votlage is too low, using PV or grid to charge the
too low
battery;
3. Seek help from us, if can not go back to normal state.
1. ARC fault detection is only for US market;
F63
ARC fault
2. Check PV module cable connection and clear the fault;
3. Seek help from us, if can not go back to normal state.
Heat sink temerperature is too high
DC insulation impedance
1. Check whether the work environment temperature is too high;
F24
2. Turn off the inverter for 10mins and restart;
failure
3. Seek help from us, if can not go back to normal state.
Chart 6-1 Fault information
Under the guidance of our company, customers return our products so that our company
can provide service of maintenance or replacement of products of the same value.
Customers need to pay the necessary freight and other related costs.
Any replacement or repair of the product will cover the remaining warranty period of the
product. If any part of the product or product is replaced by the company itself during the
warranty period, all rights and interests of the replacement product or component belong
to Ningbo Deye Inverter Technology Co., Ltd.
Factory warranty does not include damage due to the following reasons:
・ Damage during transportation of equipment;
・ Damage caused by incorrect installation or commissioning;
・ Damage caused by failure to comply with operation instructions, installation
instructions or maintenance instructions;
・ Damage caused by attempts to modify, alter or repair products;
・ Damage caused by incorrect use or operation;
・ Damage caused by insufficient ventilation of equipment;
・ Damage caused by failure to comply with applicable safety standards or regulations;
・ Damage caused by natural disasters or force majeure (e.g. floods, lightning, overvoltage,
storms, fires, etc.)
In addition, normal wear or any other failure will not affect the basic operation of the
product. Any external scratches, stains or natural mechanical wear does not represent
a defect in the product.
Solutions
- 31 -
8.Limitation of Liability
In addition to the product warranty described above, the state and local laws and regulations
provide financial compensation for the product's power connection (including violation of
implied terms and warranties). The company hereby declares that the terms and conditions
of the product and the policy cannot and can only legally exclude all liability within a limited
scope.
9. Datasheet
SUN-3.6K-SG03LP1
Technical Data
Battery Type
Battery Voltage Range (V)
Max. Charging Current (A)
Max. Discharging Current (A)
Charging Curve
External Temperature Sensor
Charging Strategy for Li-Ion Battery
Max. DC Input Power (W)
PV Input Voltage (V)
MPPT Range (V)
Full Load DC Voltage Range
Start-up Voltage (V)
PV Input Current (A)
No. of MPPT Trackers
No. of Strings per MPPT Tracker
Rated AC Output and UPS Power (W)
Max. AC Output Power (W)
Peak Power(off grid)
AC Output Rated Current(A)
Max. AC Current(A)
Max Continuous AC Passthrough (A)
SUN-5K-SG03LP1
-EU
-EU
Lead-acid or Li-lon
40V-60V
90A
120A
90A
120A
3 Stages/equalization
Optional
Self-adaption to BMS
4680W
6500W
370V(100V~500V)
125~425V
240V~425V
150V
11A+11A
2
1/1
3600W
5000W
3960W
5500W
2 times of rated power, 10 S
15.7A
21.7A
18A
25A
35A
- 32 -