DeZurik M3 Manuale - Pagina 10
Sfoglia online o scarica il pdf Manuale per Controllore DeZurik M3. DeZurik M3 11.
DeZURIK
M-Series Manual Actuator
Troubleshooting
Symptom
Actuator closes to wrong position.
Actuator opens to wrong position.
Actuator won't close.
Wrenching square turns, but
actuator doesn't turn.
Actuator turns, but valve doesn't.
Rotation direction of wrenching
square is incorrect.
D10287
Possible Cause
Closed position stop is set
incorrectly.
Open position stop is set
incorrectly.
Obstruction in valve is
preventing closure.
Pin in wrenching square is
sheared.
Valve shaft key in yoke is
sheared.
Yoke-to-shaft key is 90° off.
Page 10
Corrective Action
Adjust closed position stop.
Adjust open position stop.
Remove obstruction.
Replace pin.
Replace key.
Disengage actuator yoke from
valve shaft, turn 90° and
re-engage.
February 2017