2VV IC-ModBus Manuale di installazione e assistenza - Pagina 8

Sfoglia online o scarica il pdf Manuale di installazione e assistenza per Controllore 2VV IC-ModBus. 2VV IC-ModBus 13.

7. CONTROL

7.1. COMMUNICATION PROTOCOL - MODBUS RTU

*Address of module 0x01
Operational parameters of communication line RS485 MODBUS (RTU):
9600Bd
1 start bit
8 data bits
1 bit even parity
1 stop bit
Each module must support even parity. If parity is not used, it is replaced by second stop bit.
Communication method:
Master – control system (BMS)
Slave – electronics Module D (Modbus module)
Only the control system can be connected.
After the first connection of power supply, the module is in the OFF state. The requested operational mode must be sent by the superior control system! After
the subsequent disconnection of the power supply, the module remembers its last operational mode.
Communication connector numbers:
A - 6
B - 7
GND - 8
MODBUS RTU:
In the RTU mode, every 8-bit byte of message contains two 4-bit hexadecimal characters. The transmission of a message must be continuous, the spaces
between the characters must not be longer than 1.5 character. The beginning and end of the message is identified according to the bus rest longer than 3.5
character. The RTU frame format is shown in the picture.
General structure of telegram [hex]:
Beginning
> 3.5 characters
Data block length
Size of ADU on RS-485 = 253 bytes PDU + address(1 byte) + CRC (2 bytes) = 256 bytes
Address
Master has not any specific address, only slave units have to have an address unique in all MODBUS site.
CRC
Field with generating polynom x16 + x15 + x2 + 1.
7.2. TABLE OF KEY CHARACTERS AND CONFIGURATION DATA
Factory Driver:
Intended for hardware setup (READ/WRITE)
Address
10001
10002
10003
10004
10005
10006
At the IC-ModBus regulator, it is necessary to always set AC5 on address 10001 (five-degree module)
8
Address
Function
8 bits
8 bits
Name
Factory set register - without valid FactoryPass only read
0 - AC3
AC_Switch
1 - AC5
MaxFlowManual
% of fan power
MinFlowManual
% of fan power
0 - none
Postheat_1
1 - electric
2 - water
0 - PWM
MotorEC_set
1 - analog (0-10V)
0 - non
TempEXT1
1 - used
2VV. Creating innovative solutions for you and your business since 1995.
Data
CRC
N * 8 bits
16 bits
Info
Min. Value
0
70
0
0
0
0
End
> 3.5 characters
Max. Value
Default
1
100
40
2
1
1
0
100
20
0
0
0