CPG 351CPGSPR18N Manuale d'uso - Pagina 5

Sfoglia online o scarica il pdf Manuale d'uso per Gamme CPG 351CPGSPR18N. CPG 351CPGSPR18N 13. Stock pot range

CPG 351CPGSPR18N Manuale d'uso
USER MANUAL
GAS CONNECTION
The gas supply (service) line must be the same size or greater than the inlet line of the appliance. Cooking
Performance Group appliances use a ¾" NPT inlet. Sealant on all pipe joints must be resistive to liquid
propane or natural gas. This range uses NG32 and LP49 connections for gas nozzles.
MANUAL SHUT OFF VALVE
This installer supplied valve must be in the gas service line ahead of the appliance regulator in the gas stream
and in a position accessible in the event of an emergency.
PRESSURE REGULATOR
Commercial cooking equipment must have a pressure regulator on the incoming service line for safe and
efficient operation, since service pressures may fluctuate on local demand. A pressure regulator is packed
inside every Cooking Performance Group appliance.
FAILURE TO INSTALL THE PRESSURE REGULATOR WILL VOID THE APPLIANCE WARRANTY.
The regulators supplied along with Cooking Performance Group appliances, will have ¾" inlet/outlet
openings and are adjusted at the factory for 4" WC (natural gas) or 10" WC (liquid propane gas) depending on
customer's ordering instructions.
Prior to connecting the regulator, check the incoming line pressure, as these regulators can only withstand
a maximum pressure of ½'' psi (14" WC). If the line pressure is beyond this limit, a step down regulator
will be required.
The arrow shown on the bottom of the regulator body shows the gas flow direction, it should point
downstream to the appliance. The red air vent cap on the top is part of the regulator and should
not be removed.
Any adjustments to the regulator should be made only by qualified service personnel with the
proper equipment.
HI/LOW Fan Speed:
Use to select fan speed (HI or
CONNECTIONS
LOW). The appropriate speed is
Please check installer supplied intake pipes visually and / or blow them with compressed air to clear any dirt
determined by the type of food
particles, threading chips or any other foreign matter before installing a service line. When gas pressure is
being cooked.
applied, these particles could clog orifices. All connections must be sealed with a joint compound suitable for
LP and natural gas, and all connections must be tested with a soapy water solution before lighting any pilots.
www.CookingPerformanceGroup.com
1-800-678-5517
All manuals and user guides at all-guides.com
5