2. Turn Speed Control switch clockwise past the click at the "HIGH" setting to turn power "ON".
3. Set Speed Control switch to desired setting.
Note: Refer to the chart in this instruction manual entitled PAS1200 SPECIFICATIONS that lists the
airflows for the PAS1200.
Note: In the event of a power failure while the unit is running, or loss of power due to any other cause, after a
brief delay this unit's motorized impeller will re-start when power is restored.
TRANSPORTING THE UNIT
The PAS1200 Portable Air Scrubber should be secured to ensure that the unit does not roll during transport and
can be transported in the horizontal position. If extremely poor road conditions exist, or excessive shock and
vibration are expected, take precautionary measures by padding the unit to provide impact absorption during
transport.
Caution: Always use caution when moving the PAS1200 Portable Air Scrubber inside a building or home.
The unit weighs 85 pounds. Older structures with weakened floors or staircases may require special
considerations for safe transport.
USER SERVICING INSTRUCTIONS
Abatement Technologies' portable air scrubbers are designed to be low maintenance devices and basic
maintenance should be performed as follows:
Filters should be changed as needed based on the filter change indicator light. Follow the FILTER
•
CHANGE PROCEDURE as described in this manual. Filters can be changed earlier, if desired, to
maintain a minimum required flow rate.
The unit should be cleaned with a damp cloth or a water-based cleaner/sanitizer as needed. Do not use
•
harsh chemicals, solvents, or detergents to clean the unit.
Warning: Keep electrical components dry as their exposure to liquids poses a safety hazard and can damage
components.
FILTER REPLACEMENT
Note: Personnel responsible for changing filters, servicing units or relocating units within the facility are urged to
wear the proper personal protective equipment (PPE) and follow safe work practices in accordance with federal,
state, provincial, local and employer regulations. Abatement Technologies cannot recommend the type of PPE
required as that will need to be determined by safety/risk assessment personnel based on various risk factors,
including the type of particulates being captured by the air filtration device and the surrounding environment
where the units are being used, transported, or serviced.
Note: Filters being replaced must be disposed of in accordance with federal, state, provincial, local, and facility
regulations.
System airflow reduction is generally the result of filter loading, blockage of the unit's inlet, or use of excessive
lengths of flex duct.
The size and concentration of airborne contaminants, temperature and humidity conditions, and duration of use
determine how often filters need replacement. If the Primary Filter Change Indicator on the control panel
illuminates, this indicates one or more of the following: (1) pre-filter(s) are loaded, (2) the inlet is obstructed,
and/or (3) the flex duct, if attached to inlet, is too long or has too many bends. If the HEPA Filter Change Indicator
on the control panel illuminates, this indicates one or more of the following: (1) HEPA filter is loaded, (2) the inlet
or outlet is obstructed, and/or the flex duct, if attached, is too long or has too many bends.
7