Dell EMC VxRail S Series Manuale d'uso - Pagina 23

Sfoglia online o scarica il pdf Manuale d'uso per Server Dell EMC VxRail S Series. Dell EMC VxRail S Series 32.

Dell EMC VxRail S Series Manuale d'uso
Table 22. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Table 23. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Standard operating temperature

The standard operating temperature for altitude less than 950 meters or 3117 feet ranges from 10°C to 35°C (50°F to 95°F) with no
direct sunlight on the equipment.

Expanded operating temperature

Table 24. Expanded operating temperature specifications
Expanded operating temperature
Continuous operation
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE:
This condition applies only to data center
environments. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or
MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data
center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point
less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data
center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C
to 35°C), the appliance can operate continuously in
temperatures as low as 5°C and as high as 40°C.
Technical specifications
23