EarthLinked HCM-1860C Manuale di installazione e manutenzione - Pagina 5

Sfoglia online o scarica il pdf Manuale di installazione e manutenzione per Condizionatore d'aria EarthLinked HCM-1860C. EarthLinked HCM-1860C 13. Hybrid cooling module

Inhalation of high concentrations of refrigerant gas vapor is harmful
and may cause heart irregularities, unconsciousness or death. Vapor
reduces oxygen available for breathing and is heavier than air.
Decomposition products are hazardous. Liquid contact can cause
frostbite. Avoid contact of liquid with eyes and prolonged skin
exposure. Liquid and gas are under pressure. Deliberate inhalation of
refrigerant gas is extremely dangerous. Asphyxiation can occur
without warning due to lack of oxygen. Before working with a
refrigerant, read the Materials Safety Data Sheet for that specific
refrigerant.
The dimensions data for the Hybrid Cooling Module is shown in Figure 1.
Dimensions,
Inches
H
W
21-1/2
32-1/2
12-1/2
Fan
Type
RPM
3 blade
830
Figure 1. Hybrid Cooling Module Dimensions and Data
HCM-IMM (10/16)
WARNING!
Connections
Tube, OD,
inches
D
Inlet
Outlet
7/8
7/8
Dia., inches
16
Net
Sound,
Weight,
dB(A)
Lbs
56.0
38
Electrical
Power
Fan HP
230-1-50/60
1/8
Coil
Active
Fins/inch
Area,
Rows
Sq Ft
1
14
4.375
Fan FLA
Min Voltage
0.35
207
Face
5