Dell S4810-ON Manuale di installazione - Pagina 27
Sfoglia online o scarica il pdf Manuale di installazione per Interruttore Dell S4810-ON. Dell S4810-ON 42.
Fans
The S4810–ON comes from the factory with one power supply unit (PSU) and two fan modules installed
in the system.
If two or more fans are installed and running, the fan modules are hot-swappable.
NOTE: To run the system, both slots must have operating fan units. If a module is not installed in
each slot (either as part of the PSU or as an independent fan module), the system shuts down in one
minute.
In addition to the integrated fan/power supply modules, you can order and install fan modules separately.
The S4810–ON supports two airflow direction options. Do not mix airflow types in a chassis; you can use
only a single airflow direction in a chassis.
•
Normal — airflow is from the I/O panel to the PSU
•
Reversed — airflow is from the PSU to the I/O panel
Environmental factors can decrease the amount of time required between fan replacements. Check the
environmental factors regularly. An increase in temperature and/or particulate matter in the air might
affect performance (for example, new equipment installation).
CAUTION: Check the fans at six-month intervals and replace them as necessary. Regularly
monitor the speeds of the cooling fans in order to accurately determine replacement intervals.
Components
The following are the S4810–ON fan components.
•
S4810–ON Fan module
•
S4810–ON Fan module - Reverse flow
Fans
6
27