ABB ACS880-01 Series Manuale di installazione e avviamento rapido - Pagina 12
Sfoglia online o scarica il pdf Manuale di installazione e avviamento rapido per Apparecchiature industriali ABB ACS880-01 Series. ABB ACS880-01 Series 17. Industrial drives
Anche per ABB ACS880-01 Series: Manuale di installazione (20 pagine), Manuale di installazione rapida (14 pagine), Manuale (16 pagine), Manuale d'uso (18 pagine)
Warning
Fault
Aux. code
-
FA81
Safe torque off 1 loss
-
FA82
Safe torque off 2 loss
Ratings, fuses and typical power cables
1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses. See hardware manual for guidelines in selecting between aR and gG
fuses, and for additional fuse alternatives
3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274
certifications. Refer to note 6 for circuit breaker protection.
4) IEC 61439-1: The drive is suitable for use on a circuit capable of delivering not more than 65 kA when protected by the
fuses given in this table.
5) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100 kA
symmetrical amperes (rms) at 600 V maximum when protected by the ABB recommended fuses.
6) Refer to
Alternate Fuses, MMPs and Circuit Breakers for ABB Drives
and circuit breakers that can be used as branch circuit protection.
7) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings.
8)IEC 61800-9-2: Typical drive losses when it operates at 90% of the nominal output frequency and 100% of the nominal
output current.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-
52/2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
10) NEC Installations: The cable sizing is based on NEC Table 310-15 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly
buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
ACS880
Frame
Nominal ratings
-01-...
size
Input
Output
current
current
I
1
A
U
= 3-phase 230 V
n
04A6-2
R1
4.6
06A6-2
R1
6.6
07A5-2
R1
7.5
10A6-2
R1
10.6
16A8-2
R2
16.8
24A3-2
R2
24.3
031A-2
R3
31.0
046A-2
R4
46
061A-2
R4
61
075A-2
R5
75
087A-2
R5
87
115A-2
R6
115
145A-2
R6
145
170A-2
R7
170
206A-2
R7
206
274A-2
R8
274
U
= 3-phase 400 V
n
02A4-3
R1
2.4
03A3-3
R1
3.3
04A0-3
R1
4.0
05A6-3
R1
5.6
07A2-3
R1
8.0
09A4-3
R1
10.0
12A6-3
R1
12.9
017A-3
R2
17.0
025A-3
R2
25.0
032A-3
R3
32.0
038A-3
R3
38.0
045A-3
R4
45.0
061A-3
R4
61
072A-3
R5
72
087A-3
R5
87
105A-3
R6
105
145A-3
R6
145
169A-3
R7
169
206A-3
R7
206
246A-3
R8
246
Description
The Safe torque off circuit 1 is broken.
The Safe torque off circuit 2 is broken.
.
Motor
gG fuse
1)
power
(DIN 43620)
I
P
ABB type
2
n
A
kW
hp
4.6
0.75
1.0
OFAF000H6
6.6
1.1
1.5
OFAF000H10
7.5
1.5
2.0
OFAF000H16
10.6
2.2
3.0
OFAF000H16
16.8
4.0
5.0
OFAF000H25
24.3
5.5
7.5
OFAF000H40
31.0
7.5
10
OFAF000H50
46
11
11
OFAF000H63
61
15
20
OFAF000H80
75
18.5
25
OFAF000H100
87
22
30
OFAF00H125
115
30
40
OFAF00H160
145
37
50
OFAF0H200
170
45
60
OFAF0H250
206
55
75
OFAF1H315
274
75
100
OFAF2H400
2.4
0.75
-
OFAF000H4
3.3
1.1
-
OFAF000H6
4.0
1.5
-
OFAF000H6
5.6
2.2
-
OFAF000H10
8.0
3.0
-
OFAF000H10
10.0
4.0
-
OFAF000H16
12.9
5.5
-
OFAF000H16
17.0
7.5
-
OFAF000H25
25.0
11.0
-
OFAF000H32
32.0
15.0
-
OFAF000H40
38.0
18.5
-
OFAF000H50
45.0
22.0
-
OFAF000H63
61
30
-
OFAF000H80
72
37
-
OFAF000H100
87
45
-
OFAF000H100
105
55
-
OFAF00H125
145
75
-
OFAF00H160
169
90
-
OFAF0H250
206
110
-
OFAF1H315
246
132
-
OFAF1H355
(3AXD50000645015
3)
Fuses
4)
2)4)
aR fuse
UL class
5)6)7)
(DIN 43620)
T
Bussmann type
170M1559
JJS-15
170M1559
JJS-15
170M1559
JJS-15
170M1560
JJS-20
170M1561
JJS-25
170M1563
JJS-35
170M1565
JJS-50
170M1566
JJS-80
170M1568
JJS-80
170M3815
JJS-110
170M3816
JJS-110
170M3817
JJS-150
170M3817
JJS-200
170M5809
JJS-250
170M5810
JJS-300
170M5810
JJS-400
170M1561
-
170M1561
-
170M1561
-
170M1561
-
170M1561
-
170M1561
-
170M1561
-
170M1563
-
170M1563
-
170M1565
-
170M1565
-
170M1566
-
170M1567
-
170M1568
-
170M1569
-
170M3817
-
170M3817
-
170M5809
-
170M5810
-
170M5812
-
[English]) for additional UL fuses
Typical
Typical power cable
power loss
Copper
2 9)
10)
mm
AWG
3×1.5
14
3×1.5
14
3×1.5
14
100
3×1.5
14
3×6
10
3×6
8
372
3×10
8
364
3×16
6
3×25
4
3×35
3
955
3×35
2
1177
3×50
1/0
1378
3×95
3/0
1946
3×120
4/0
1986
2×150
300 MCM
2660
2×(3×95)
2×2/0
3472
3×1.5
-
3×1.5
-
3×1.5
-
3×1.5
-
3×1.5
-
3×1.5
-
149
3×1.5
-
3×6
-
239
3×6
-
3×10
-
406
3×10
-
519
3×16
-
533
3×25
-
820
3×35
-
865
3×35
-
1157
3×50
-
1228
3×95
-
1965
3×120
-
2049
3×150
-
2812
2×(3×70)
-
3049
12
8)
W
61
88
152
216
551
811
47
55
63
81
115
217
411