When pressing button, display shows the pre-set rated value
(+2° C factory set).
Additional pressing of button
Pressing button for approx. 2 sec. brings the device into the energy
saving mode and the LED "ECO" lights.
The following parameters change in the energy saving mode :
1) Evaporator ventilating fan works in cycles only
2) Automatic defrost starts every 8 hours only instead of every 6 hours
3) The rated value is increased acc. to pre-set factory values
(from +4° C to +6° C)
Rated value in ECO-mode can be changed by pressing button
or
.
In periods of few or none door openings (closing day, at night, holidays ) energy
consumption may be reduced considerably by this mode.
3.2 Defrosting
All refrigerators dispose of a fully automatic defrost regulation. The parameters for
defrost intervals, defrost times etc. are factory pre-set to the optimum values.
Parameters may be adjusted by refrigeration / electric specialist only if need be.
On request parameter lists are available from the manufacturer.
During defrosting "DEF" lights up on the display. This signals the defrosting phase
and goes out again when defrosting process has been finished.
All refrigerated counters with built-in cooling system evaporate the condensate
automatically by hot gas. All refrigerated counters for connection to a central
cooling system discharge the condensate via given siphon outlets into the build-
ing lines (see page 17, picture 4).
Attention: Do not pour any cleaning water, other liquids, food particles or similar
into the condensate discharge. This would impede the fully automatic defrost
and evaporation function of your refrigerated counter. Check regularly if the
condensate flows unhindered through the drainpipe (see page 17, picture 2).
temperature 10° C beyond set rated value
temperature 10° C less than set rated value
door open for more than 2 minutes
high pressure compressor (devices with built-in
refrigeration machine only)
probe T1 defective
probe T2 defective
clean the condenser
or